一、 新型室外一体化节能机柜产品简介 ...................................................................................................................... 5 二、 一体化户外机柜产品介绍 ...................................................................................................................................... 6 1、热交换型: .................................................................................................................................................................... 6 2、压缩机空调型: ............................................................................................................................................................ 6 3、柜体基本配置: ............................................................................................................................................................ 6 三、柜体安装示意图: ...................................................................................................................................................... 6 四、一体化户外柜安装: .................................................................................................................................................. 7 五、一体化户外柜部件清单: .......................................................................................................................................... 7 六、一体化户外机柜安装分解图: .................................................................................................................................. 8 1、将底座安装到基座上:................................................................................................................................................. 8 2、先将设备舱安装到底座上:............................................................................................................................................ 8

2、先将设备舱安装到底座上: .................................................................. ......................................... 8 3、再将电源舱安装到底座上: .......................................................................................................... 10 4、将电池舱安装到底座上,并通过柜顶接接件将各舱体紧固在一起: ....................................... 10 5、最后将顶盖装配到机柜顶上,并用螺丝坚固: .......................................................................... 11

七、交流配电、接地、防雷原理应用 ............................................................................................................................ 12 八、蓄电池柜的应用说明 ................................................................................................................................................ 13 九、监控配置 .................................................................................................................................................................... 14 十、电源柜配置介绍 ........................................................................................................................................................ 15 十一、设备机柜配置介绍 ................................................................................................................................................ 16 十二、安装布线要求: .................................................................................................................................................... 16 十三、免责条款 ................................................................................................................................................................ 17 十四、客户支持 ................................................................................................................................................................ 17

一、新型室外一体化节能机柜产品简介

新型室外一体化节能机柜是一款安全、可靠、防盗性能较强、噪音低、散热效果好、占用空间小的好产品。此产品还有一特点就是可以满足快速建站,把产品输送到站点,把三个舱体安装完成后,把电源线与预留好端子对接,电源,热交换器,空调,等设备就可以使用,无需现场安装布线。一体化机柜适合在室外环境,如公路边、公园、楼顶、山区、平地安装的机柜,机柜内可安装基站设备、电源设备、蓄电池、温控设备、传输设备及其他配套设备或为以上设备预留安装空间及换热容量,能为内部设备正常运行提供可靠的机械和环境保护的机柜。一体化机柜由蓄电池柜、电源柜、设备柜组成,充分利用每个机柜内部可用空间。户外机柜选址时选择通风较好的区域,安装于空旷地带或楼面上,尽量不要安装于居民楼道内或居民房间内,以免影响通风散热效果,以及设备运行行噪音扰民;安装时必须有可靠的槽钢底座或水泥墩座,远离低洼地带及高粉尘区域,有合格的接地排。

一、 一体化户外机柜产品介绍

1、

热交换型:

采用热交换器作为散热设备的温控元件,利用内外完全隔离的风道,通过相互隔绝的热交换器芯传递热量的散热方式。

2、 3、

压缩机空调型:

制冷单元采用不低于300W制冷量的压缩机空调,制冷能效比(EER)在2.0以上。

柜体基本配置:

一体化机柜的组件、部件、零件、附属设备及其安装接口,都是标准的、通用的。主要由金属材料制成,采用落地式安装方式的柜体,其内部可安装主设备(BBU)和交、直防雷、传输设备、电源、温控设备及其他配套设备,方便维护,并能为内部设备正常工作提供可靠的机械和环境保护的柜体。机柜内部设置4 根安装立柱,用于安装设备和固定层板。安装立柱能够前后移动调节。机柜的外部无裸露螺丝,避免通过外部拆卸而形成偷盗;机柜采用同底座结构,并配有同一遮阳罩,以避免柜间漏雨而引起的腐蚀现象,设备、电源机柜柜门采用对开门方式。

二、 柜体安装示意图:

(左柜电池舱、中柜电源舱、右柜设备舱)

一体化户外柜底视图 (左柜电池舱、中柜电源舱、右柜设备舱)

三、 一体化户外柜安装:

安装场所

根据网络规划的需要,一体化机柜可安装在地面、楼顶、路边、山坡等地区,可贴近地面安装,也可架空安装;在安装在洪水多发区域时,需考虑防洪要求。

组装方式

一体化机柜能同时支持整装式(整装发货现场吊装)和拼装式(散件发货现场拼装)两种组装方式。 整装式

根据需要,整装式一体化机柜在生产工厂、库房集成安装。其能适陆运、海运或空运的需要,满足运输过程中颠簸、振动、提吊的要求。

拼装式

根据需要,可将一体化机柜的零部件运输到现场,现场进行标准化拼装。

四、 一体化户外柜部件清单:

五、 一体化户外机柜安装分解图:

1、 将底座安装到基座上:

4、 将设备舱安装到底座上,并通过柜顶接接件将各舱体紧固在一起:

5、 最后将顶盖装配到机柜顶上,并用螺丝坚固:

六、 交流配电、接地、防雷原理应用

室外一体化机柜的交流侧提供B+C级防雷装置。机柜设置接地排,机柜的金属部分互连并接至接地排, 防雷器的接地线必须有良好的导通能力。具有双路电源(市电/油机)手动转换装置,转换方式为采用2个开关机械互锁手动操作。机柜配置油机专用M6接线端子,安装接线较为方便。

交流配电电气原理及示意图

七、 蓄电池柜的应用说明

电池柜简介

可安装外尺寸为650mm(W)×700mm(D)×1200mm(H) (不含底座、不含遮阳罩高度,不含压缩机

空调凸出部分),可安装2组12V/150AH蓄电池组,柜内支架分层安装,每层能承受不小于5kN/m2的均匀荷载。电池安装完毕后,请将电池二次防防盗档板装上,以起到双重防盗作用。

八、 监控配置

机柜空调具有RS232或RS485通信接口,通过该接口可对温控单元的温度设定值进行调整以及对温度告警设定值进行调整,并能送出柜内外的温度参数和各种故障告警信息。

遥测:柜内温度、柜外温度。

遥信:电源故障告警,温度探头状态(故障/正常),温控单元状态(故障/正常),柜门状态(开门/关门)、高压告警、低压告警、高压持续告警、低压持续告警、柜内高温告警、柜内低温告警、柜外高温告警、柜外低温告警、电源频偏告警、自定义告警(烟雾告警)。

遥控:能对空调参数进行远程设置或开关机。

监控报警上传接线说明

OUT1:高温+水浸告警

OUT2:整流模块告警

OUT3:电池低压告警

OUT4:门禁告警

OUT5:烟感告警

OUT6:市电掉电告警

干接点正常情况了闭合,开路时报警。

电源柜采用热交换方式进行柜内设备运行散热,主要安装包括交流市电引入、市电/油机电转换、高频开关电源(直流配电)、防雷装置、ODF及其它设备等。机柜内支持19英寸(IEC297)标准机架,以及支持符合19英寸(IEC297)尺寸安装空间要求的各种设备(如电源设备、基站设备、传输设备、温控设备、蓄电池、防雷设备及其它配套设备)的安装。

热交换器

热交换器由独立的两个空气循环组成,当位于机柜侧空气温度高于机柜外部环境空气温度时,热交换器可以实现机柜的散热。热交换器的主控板和内外循环风机采用-48V DC供电。为保证温控设备的可靠性,同时节约能耗,热交换器、风扇转速根据柜内温度进行自动调节。

高频开关电源

主要是满足机柜通信设备-48V直流供电需要,采用插框式高频开关电源,标准机柜式安装,本配置整流模块电流系列为:50A,模块数量4个,交流输入额定输入电压: AC 220V,单相三线制,输入电压允许变动范围:90V~290V,输入频率范围:50Hz±10%,输出电压在48V~56.4V范围。蓄电池组接入:系统能接入两组蓄电池,当其中一组不能工作时,另外一组能正常供电。

可安装外尺寸为650mm(W)×700mm(D)×1200mm(H) (不含底座、不含遮阳罩高度),采用热交换方式对柜内设备进行散热,主要安装包括直流配电、传输、DDF、BBU等设备等。机柜内支持19英寸(IEC297)标准机架,以及支持符合19英寸(IEC297)尺寸安装空间要求的各种设备(如电源设备、基站设备、传输设备、温控设备、蓄电池、防雷设备及其它配套设备)的安装。

热交换器

热交换器由独立的两个空气循环组成,当位于机柜侧空气温度高于机柜外部环境空气温度时,热交换器可以实现机柜的散热。热交换器的主控板和内外循环风机采用-48V DC供电。为保证温控设备的可靠性,同时节约能耗,热交换器、风扇转速根据柜内温度进行自动调节。

直流配电

1)直流配电安装于设备柜内,将一次下电、二次下电整合到一个模块。

2)二次下电配电单元机架式安装主要供电设备包括传输设备、BBU设备等重要设备。

3)一次下电配电单元机架式安装,主要供电设备包括RRU及机柜内配置的辅助设备等重要设备。 直流配电一次下电、二次下电模块电气原理及示意图

十一、 安装布线要求:

一体化机柜过线区预留足够的空间以满足机柜满配要求, 柜与柜之间的配线由厂家配置,包括电源线、信号线等的连接线,线缆必须绑扎好。

十二、 免责条款

以下情况之一均不属免费维修范围:

·免费保修期外;

·人为故障;

·未经受权私自拆开产品或修改;

·违反产品操作或使用规定;

·产品在客户那里遭到不可抗拒或其它外来因素而引起的损坏或损失。

·保修期内,因维修造成的运输费用由用户承担,如产品发生故障,请用户及时与我们联系。 十三、 客户支持

本指引的解释权归本公司。

一体化户外机柜

----产品安装规范----

目录

一、 新型室外一体化节能机柜产品简介 ...................................................................................................................... 5 二、 一体化户外机柜产品介绍 ...................................................................................................................................... 6 1、热交换型: .................................................................................................................................................................... 6 2、压缩机空调型: ............................................................................................................................................................ 6 3、柜体基本配置: ............................................................................................................................................................ 6 三、柜体安装示意图: ...................................................................................................................................................... 6 四、一体化户外柜安装: .................................................................................................................................................. 7 五、一体化户外柜部件清单: .......................................................................................................................................... 7 六、一体化户外机柜安装分解图: .................................................................................................................................. 8 1、将底座安装到基座上:................................................................................................................................................. 8 2、先将设备舱安装到底座上:............................................................................................................................................ 8

2、先将设备舱安装到底座上: .................................................................. ......................................... 8 3、再将电源舱安装到底座上: .......................................................................................................... 10 4、将电池舱安装到底座上,并通过柜顶接接件将各舱体紧固在一起: ....................................... 10 5、最后将顶盖装配到机柜顶上,并用螺丝坚固: .......................................................................... 11

七、交流配电、接地、防雷原理应用 ............................................................................................................................ 12 八、蓄电池柜的应用说明 ................................................................................................................................................ 13 九、监控配置 .................................................................................................................................................................... 14 十、电源柜配置介绍 ........................................................................................................................................................ 15 十一、设备机柜配置介绍 ................................................................................................................................................ 16 十二、安装布线要求: .................................................................................................................................................... 16 十三、免责条款 ................................................................................................................................................................ 17 十四、客户支持 ................................................................................................................................................................ 17

一、新型室外一体化节能机柜产品简介

新型室外一体化节能机柜是一款安全、可靠、防盗性能较强、噪音低、散热效果好、占用空间小的好产品。此产品还有一特点就是可以满足快速建站,把产品输送到站点,把三个舱体安装完成后,把电源线与预留好端子对接,电源,热交换器,空调,等设备就可以使用,无需现场安装布线。一体化机柜适合在室外环境,如公路边、公园、楼顶、山区、平地安装的机柜,机柜内可安装基站设备、电源设备、蓄电池、温控设备、传输设备及其他配套设备或为以上设备预留安装空间及换热容量,能为内部设备正常运行提供可靠的机械和环境保护的机柜。一体化机柜由蓄电池柜、电源柜、设备柜组成,充分利用每个机柜内部可用空间。户外机柜选址时选择通风较好的区域,安装于空旷地带或楼面上,尽量不要安装于居民楼道内或居民房间内,以免影响通风散热效果,以及设备运行行噪音扰民;安装时必须有可靠的槽钢底座或水泥墩座,远离低洼地带及高粉尘区域,有合格的接地排。

一、 一体化户外机柜产品介绍

1、

热交换型:

采用热交换器作为散热设备的温控元件,利用内外完全隔离的风道,通过相互隔绝的热交换器芯传递热量的散热方式。

2、 3、

压缩机空调型:

制冷单元采用不低于300W制冷量的压缩机空调,制冷能效比(EER)在2.0以上。

柜体基本配置:

一体化机柜的组件、部件、零件、附属设备及其安装接口,都是标准的、通用的。主要由金属材料制成,采用落地式安装方式的柜体,其内部可安装主设备(BBU)和交、直防雷、传输设备、电源、温控设备及其他配套设备,方便维护,并能为内部设备正常工作提供可靠的机械和环境保护的柜体。机柜内部设置4 根安装立柱,用于安装设备和固定层板。安装立柱能够前后移动调节。机柜的外部无裸露螺丝,避免通过外部拆卸而形成偷盗;机柜采用同底座结构,并配有同一遮阳罩,以避免柜间漏雨而引起的腐蚀现象,设备、电源机柜柜门采用对开门方式。

二、 柜体安装示意图:

(左柜电池舱、中柜电源舱、右柜设备舱)

一体化户外柜底视图 (左柜电池舱、中柜电源舱、右柜设备舱)

三、 一体化户外柜安装:

安装场所

根据网络规划的需要,一体化机柜可安装在地面、楼顶、路边、山坡等地区,可贴近地面安装,也可架空安装;在安装在洪水多发区域时,需考虑防洪要求。

组装方式

一体化机柜能同时支持整装式(整装发货现场吊装)和拼装式(散件发货现场拼装)两种组装方式。 整装式

根据需要,整装式一体化机柜在生产工厂、库房集成安装。其能适陆运、海运或空运的需要,满足运输过程中颠簸、振动、提吊的要求。

拼装式

根据需要,可将一体化机柜的零部件运输到现场,现场进行标准化拼装。

四、 一体化户外柜部件清单:

五、 一体化户外机柜安装分解图:

1、 将底座安装到基座上:

4、 将设备舱安装到底座上,并通过柜顶接接件将各舱体紧固在一起:

5、 最后将顶盖装配到机柜顶上,并用螺丝坚固:

六、 交流配电、接地、防雷原理应用

室外一体化机柜的交流侧提供B+C级防雷装置。机柜设置接地排,机柜的金属部分互连并接至接地排, 防雷器的接地线必须有良好的导通能力。具有双路电源(市电/油机)手动转换装置,转换方式为采用2个开关机械互锁手动操作。机柜配置油机专用M6接线端子,安装接线较为方便。

交流配电电气原理及示意图

七、 蓄电池柜的应用说明

电池柜简介

可安装外尺寸为650mm(W)×700mm(D)×1200mm(H) (不含底座、不含遮阳罩高度,不含压缩机

空调凸出部分),可安装2组12V/150AH蓄电池组,柜内支架分层安装,每层能承受不小于5kN/m2的均匀荷载。电池安装完毕后,请将电池二次防防盗档板装上,以起到双重防盗作用。

八、 监控配置

机柜空调具有RS232或RS485通信接口,通过该接口可对温控单元的温度设定值进行调整以及对温度告警设定值进行调整,并能送出柜内外的温度参数和各种故障告警信息。

遥测:柜内温度、柜外温度。

遥信:电源故障告警,温度探头状态(故障/正常),温控单元状态(故障/正常),柜门状态(开门/关门)、高压告警、低压告警、高压持续告警、低压持续告警、柜内高温告警、柜内低温告警、柜外高温告警、柜外低温告警、电源频偏告警、自定义告警(烟雾告警)。

遥控:能对空调参数进行远程设置或开关机。

监控报警上传接线说明

OUT1:高温+水浸告警

OUT2:整流模块告警

OUT3:电池低压告警

OUT4:门禁告警

OUT5:烟感告警

OUT6:市电掉电告警

干接点正常情况了闭合,开路时报警。

电源柜采用热交换方式进行柜内设备运行散热,主要安装包括交流市电引入、市电/油机电转换、高频开关电源(直流配电)、防雷装置、ODF及其它设备等。机柜内支持19英寸(IEC297)标准机架,以及支持符合19英寸(IEC297)尺寸安装空间要求的各种设备(如电源设备、基站设备、传输设备、温控设备、蓄电池、防雷设备及其它配套设备)的安装。

热交换器

热交换器由独立的两个空气循环组成,当位于机柜侧空气温度高于机柜外部环境空气温度时,热交换器可以实现机柜的散热。热交换器的主控板和内外循环风机采用-48V DC供电。为保证温控设备的可靠性,同时节约能耗,热交换器、风扇转速根据柜内温度进行自动调节。

高频开关电源

主要是满足机柜通信设备-48V直流供电需要,采用插框式高频开关电源,标准机柜式安装,本配置整流模块电流系列为:50A,模块数量4个,交流输入额定输入电压: AC 220V,单相三线制,输入电压允许变动范围:90V~290V,输入频率范围:50Hz±10%,输出电压在48V~56.4V范围。蓄电池组接入:系统能接入两组蓄电池,当其中一组不能工作时,另外一组能正常供电。

可安装外尺寸为650mm(W)×700mm(D)×1200mm(H) (不含底座、不含遮阳罩高度),采用热交换方式对柜内设备进行散热,主要安装包括直流配电、传输、DDF、BBU等设备等。机柜内支持19英寸(IEC297)标准机架,以及支持符合19英寸(IEC297)尺寸安装空间要求的各种设备(如电源设备、基站设备、传输设备、温控设备、蓄电池、防雷设备及其它配套设备)的安装。

热交换器

热交换器由独立的两个空气循环组成,当位于机柜侧空气温度高于机柜外部环境空气温度时,热交换器可以实现机柜的散热。热交换器的主控板和内外循环风机采用-48V DC供电。为保证温控设备的可靠性,同时节约能耗,热交换器、风扇转速根据柜内温度进行自动调节。

直流配电

1)直流配电安装于设备柜内,将一次下电、二次下电整合到一个模块。

2)二次下电配电单元机架式安装主要供电设备包括传输设备、BBU设备等重要设备。

3)一次下电配电单元机架式安装,主要供电设备包括RRU及机柜内配置的辅助设备等重要设备。 直流配电一次下电、二次下电模块电气原理及示意图

十一、 安装布线要求:

一体化机柜过线区预留足够的空间以满足机柜满配要求, 柜与柜之间的配线由厂家配置,包括电源线、信号线等的连接线,线缆必须绑扎好。

十二、 免责条款

以下情况之一均不属免费维修范围:

·免费保修期外;

·人为故障;

·未经受权私自拆开产品或修改;

·违反产品操作或使用规定;

·产品在客户那里遭到不可抗拒或其它外来因素而引起的损坏或损失。

·保修期内,因维修造成的运输费用由用户承担,如产品发生故障,请用户及时与我们联系。 十三、 客户支持

本指引的解释权归本公司。


相关文章

  • 强电弱电工程布线施工规范与工艺ok
  • 强电弱电施工规范与工艺 一般规定 1 .本章适用于楼层单相入户配电箱户表后的室内强弱电电路布线及电 器.灯具安装. 2 .配电箱户表后应根据室内用电设备的不同功率分别配线供电:大功率家电设备应独立配线安装插座. 必须用黄绿双色线. 4 .导 ...查看


  • 机房装修施工设计方案(精品版)
  • 机房装修施工设计方案(精品版) 技 术 设 计 方 案 介 绍 设计单位:广州莱安智能化系统开发有限公司 网站:http://www.lain.com.cn 地址:广州市天河区中山大道建中路5号天河软件园海天楼3A06 用户服务中心:Tel ...查看


  • 南方供电局安健环手册
  • 南方供电局安健环技术手册 2011年7月 南网供电局安健环技术手册 目录 1. 基础概念------------------------------3 1.1安全色 1.2安全标志 1.2.1安全标志 1.2.2 设置要求 1.2.3设置方 ...查看


  • 体检中心智能化弱电改造系统实施方案
  • 视频监控系统 项目组织.实施与管理方案 第一章 项目组织 视频监控系统目前已进入施工阶段,故系统设计方案不再做,本方案主要就施工过程中的组织协调.设备材料.施工管理.操作培训及售后等方面详细说明.因视频监控系统是集多种产品的安装调试及技术支 ...查看


  • 宽带小区的几种布线设计方法
  • 摘要:近年来小区宽带化越来越热,多家电信和非电信运营商在"最后一公里"上争夺激烈.宽带正以前所未有的速度向前高速,丰富的业务提供形式和接入方式层出不穷.各种新兴的技术和运营方式的不断出现,小区宽带接入主要有以太网接入,A ...查看


  • 交通信号设备技术资料
  • 一.资质文件 1.企业资质证明(青松科技企业认证.荣誉证书一览表) 获得国家有关部门颁发的资质和国内外知名厂商出具的销售许可证明: 1.13. 400交通灯检测报告 1.14. 300交通灯检测报告 1.15. 300人行灯检测报告 1.1 ...查看


  • JH-设备安装及标签规范-模板
  •   密级: 项目名称 设备安装及标签规范 文件编号: 编 制: 何 昆 审 核: 批 准: 版 本: V1.0 颁布日期: 2014年月日 受控状态: 受控文件 文件会签页及文件内容变更记录 本文档版权归上海中信信息发展股份有限公司所有 ...查看


  • 1111通信工程规划设计方案报告格式2014
  • 重庆邮电大学 通信工程规划设计实训报告 项目名称: 专 业: 班级/小组: 组 长: 成 员: 指导教师: 2014年4月 目 录 一.设计概述 1.需求分析 ---------------------------------------- ...查看


  • 硬件大比武试题
  • 2005年技术支援部技术大比武试题 考试科目: 硬件产品 注意事项: I.A 本试卷为2005年04月大比武试题,考试时间为240分钟,总分500分,闭卷 考试. I.B 应考人员在答题前,请将姓名.工号.所在具体部门.职务认真准确地填 写 ...查看


热门内容