电压互感器开口三角接线的探讨

第38卷 第3期 电力系统保护与控制 Vol.38 No.3 2010年2月1日 Power System Protection and Control Feb.1, 2010

电压互感器开口三角接线的探讨

索保锋,王洪峰,闫志勇

(郑州供电公司,河南 郑州 450006)

摘要:介绍了在10 kV电网中,三只电压互感器开口三角接线的方法。通过向量的叠加原理,阐述了辅助绕组额定电压分别为100/3 V的四只电压互感器开口三角接线,分析了它的合理性。当三相PT辅助绕组同极性串接成三角形接线,第四只PT的辅助绕组输出电压作为零序电压时,第四只PT的辅助绕组额定电压必须为100 V。并由此探讨了由三只辅助绕组额定电压为100/3 V和一只辅助绕组额定电压为100 V构成的四只PT开口三角接线,并阐述它接线的合理性。 关键词: 电压互感器; 开口三角; 辅助绕组; 接线; 变比; 接地故障

Study of open-delta wiring in the busbar voltage transformer

SUO Bao-feng, WANG Hong-feng, YAN Zhi-yong

(Zhengzhou Power Supply Company,Zhengzhou 450006,China)

Abstract: This paper introduces the open-delta wiring of 3 PT in the 10 kV power system. It explores the open-delta wiring of four voltage transformers which rated voltage of assistant winding is 100/3V and analyzes its rationality based on vector superposition theory. The rated voltage of the forth PT’s assistant winding is must 100V when the three-phase assistant winding homopolar connects in series to the open-delta wiring and the output voltage of the forth PT’s assistant winding is regarded as zero-sequence voltage. At the same time, it discusses 4PT open-delta wiring which is made up of three assistant windings with 100/3V rated voltage and one assistant winding with 100V rated voltage, and elaborates the rationality of the wiring. Key words: voltage transformer; open-delta; assistant winding; wiring; transform ratio; earth malfunction 中图分类号: TM451 文献标识码:B 文章编号: 1674-3415(2010)03-0130-03

0 引言

在10 kV电网中,当发生单相接地,为避免引发铁磁谐振,造成PT烧坏,电压互感器普遍采用了4PT接线的方法,实际上,在现场不同的变电站,使用的电压互感器变比不同,接线方式就有不相同的地方。

1 三只单相电压互感器构成的开口三角接

线

首先,我们先回忆一下,原先在电网中3PT接线。

如图1, 在10 kV不接地系统中,单只PT的变

,正常运行时,它的开口

图1 3PT接线原理图

Fig.1 Elementary diagram of 3 single-phase voltage transformer

当发生单相接地故障时,假如A相接地,此时,A相电压输出变为0 V,B相、C相电压相位分别向下旋转了30

3Uo输出值变为3倍的相电压,如图2所示,由于单只PT

,开口三角绕组输出电压即

3Uo=3

=100 V

三角绕组输出电压,即:3Uo=Ua'+Ub'+Uc',三相电压对称平衡,开口三角绕组输出电压既3Uo=0 V。

索保锋,等 电压互感器开口三角接线的探讨 - 131

-

U'=0

UcB

Ub'

PT一次侧输入电压即为0,当一次系统三相电压不

十分平衡时, 由于辅助二次绕组接入的绕组数与理论要求的值100 V有出入,就会造成L点的电位偏

离地电位,造成开口三角形有不平衡输出,实际上,这个输出值不会很大,一般不超过3 V。

3Uo=Ua'+Ub'+Uc'=3Up

图2 A相接地时的向量

Fig.2 Vector diagram of single phase earthing

2 四只单相电压互感器构成的开口三角接线

当采用4只PT时,事情不再那么简单了: 1) 如果在原来三只PT基础上加装了与前三只相同的第四只

PT,二次接线如图3所示。

图4 第二种4PT接线二次回路原理图

Fig.4 The second kind of elementary secondary circuit of

4 single-phase voltage transformer

图3 4PT接线原理图

Fig.3 Elementary diagram of 4 single-phase voltage transformer

我们来分析一下:

3U0=UA+UB+UC=(Ua+Ul)+(Ub+Ul)+

(Uc+Ul)=Ua+Ub+Uc+3Ul

由此,就要求开口三角形接线正极性串接入第四只PT辅助二次绕组。并且第四只PT辅助二次绕组额定电压是原额定值的三倍,即100 V。

为了解决这个问题,现场作了如图4处理。 第四只PT辅助二次绕组额定电压是100/3 V,即33.3 V

V,即第四只PT二次绕组额定电压57.7 V。

即开口三角形接线正极性串接入第四只PT辅助二次绕组和第四只PT二次绕组,相当于串入第四只PT二次额定值为57.7+33.3=91 V的绕组,与理论要求的100 V比较接近。

在实际运行时,由于正常运行时,三相电压平衡,L点的电位与地电位相同(为0电位)第四只

当发生单相接地时,开口三角输出值不会因这种接线减少输出,此时,L点的电位处在接地相电压和地电位(0电位)之间。

假设接地情况为A相接地,假设两种极限情况: 一是假设L点电位为0电位,前三只PT电压三相对称,则式子3U0=UA+UB+UC=Ua+Ub+Uc+3U1中Ua+Ub+Uc=0。

第四只PT一次侧所加的电压为A相对地的电压。

3Uo=Ul=91 V

二是假设L点电位为A相电位,第4只PT电压输出为0,则式子

3U0=UA+UB+UC= Ua+Ub+Uc+3Ul中3Ul =0 这种假设其实忽略了第4只PT,3U0=UA+UB+UC= Ua+Ub+Uc=100 V

就是说,当发生单相接地时,3U0∈(91 V,100 V) 实际设备报接地故障的整定值一般为20~40 V,这种接线完全满足实际设备运行需要。

2) 如图5,这种接线,许多新参加继电保护工作的同志可能还一时接受不了,三只PT开口三角被短接,如果发生单相接地,这三只PT辅助二次绕组不就短路了吗?其实,当发生单相接地时,这三只PT辅助二次绕组中确实存在电流,但该电流不是很大,因为它只是将非故障相PT产生的电压加在故障相PT上,它只是将图3中L点的电位拉为中性电位(零电位)。由于地电位升高为单相电压,

- 132 - 电力系统保护与控制

加在第四只PT电压即为相电压。

此时,3Uo=Ul=100 V,

如果要满足以上条件,那么第四只PT的变比

。 3 另一种接线探讨

通过以上分析,可以得出另一种接线(图5)。

接线,就可以开口三角形接线正极性串接入第四只

PT辅助二次绕组,由于第四只PT辅助二次绕组额定电压为100 V,如图5所示能够满足

3U0=UA+UB+UC= Ua+Ub+Uc+3Ul

但在实际工程中,4只PT一般使用同一厂家、同一批出厂的同型号产品。故很少有四只PT变比不同的。所以这种接线在工程应用中很少见。

4 结语

[1] 梁之林,时朱大铭, 张英杰, 等. 两起GIS组合电器事

故原因分析及建议[J]. 电力设备, 2007(7):68-70.

LIANG Zhi-lin, ZHU Da-ming, ZHANG Ying-jie, et al. Case Study and Improving Suggestions for two Faults of GIS Switchgear Assembly[J]. Electrical Equipment, 2007 (7):68-70.

[2] IEC 60480-2004, Guidelines for the Checking and

Treatment of Sulfur Hexafluoride (SF6) Taken from Electrical Equipment and Specification for Its Re-use[S].

收稿日期:2008-12-01; 修回日期:2009-01-18 作者简介:

杜晓平(1978-),女,硕士,研究方向为电力系统调度自动化;

李 涛(1977-),男,硕士,研究方向为电力系统高压技术监督与设备维护;E-mail:[email protected]

陈瑞林(1975-),男,工程师,研究方向为电力系统技术管理与设备维护。

第38卷 第3期 电力系统保护与控制 Vol.38 No.3 2010年2月1日 Power System Protection and Control Feb.1, 2010

电压互感器开口三角接线的探讨

索保锋,王洪峰,闫志勇

(郑州供电公司,河南 郑州 450006)

摘要:介绍了在10 kV电网中,三只电压互感器开口三角接线的方法。通过向量的叠加原理,阐述了辅助绕组额定电压分别为100/3 V的四只电压互感器开口三角接线,分析了它的合理性。当三相PT辅助绕组同极性串接成三角形接线,第四只PT的辅助绕组输出电压作为零序电压时,第四只PT的辅助绕组额定电压必须为100 V。并由此探讨了由三只辅助绕组额定电压为100/3 V和一只辅助绕组额定电压为100 V构成的四只PT开口三角接线,并阐述它接线的合理性。 关键词: 电压互感器; 开口三角; 辅助绕组; 接线; 变比; 接地故障

Study of open-delta wiring in the busbar voltage transformer

SUO Bao-feng, WANG Hong-feng, YAN Zhi-yong

(Zhengzhou Power Supply Company,Zhengzhou 450006,China)

Abstract: This paper introduces the open-delta wiring of 3 PT in the 10 kV power system. It explores the open-delta wiring of four voltage transformers which rated voltage of assistant winding is 100/3V and analyzes its rationality based on vector superposition theory. The rated voltage of the forth PT’s assistant winding is must 100V when the three-phase assistant winding homopolar connects in series to the open-delta wiring and the output voltage of the forth PT’s assistant winding is regarded as zero-sequence voltage. At the same time, it discusses 4PT open-delta wiring which is made up of three assistant windings with 100/3V rated voltage and one assistant winding with 100V rated voltage, and elaborates the rationality of the wiring. Key words: voltage transformer; open-delta; assistant winding; wiring; transform ratio; earth malfunction 中图分类号: TM451 文献标识码:B 文章编号: 1674-3415(2010)03-0130-03

0 引言

在10 kV电网中,当发生单相接地,为避免引发铁磁谐振,造成PT烧坏,电压互感器普遍采用了4PT接线的方法,实际上,在现场不同的变电站,使用的电压互感器变比不同,接线方式就有不相同的地方。

1 三只单相电压互感器构成的开口三角接

线

首先,我们先回忆一下,原先在电网中3PT接线。

如图1, 在10 kV不接地系统中,单只PT的变

,正常运行时,它的开口

图1 3PT接线原理图

Fig.1 Elementary diagram of 3 single-phase voltage transformer

当发生单相接地故障时,假如A相接地,此时,A相电压输出变为0 V,B相、C相电压相位分别向下旋转了30

3Uo输出值变为3倍的相电压,如图2所示,由于单只PT

,开口三角绕组输出电压即

3Uo=3

=100 V

三角绕组输出电压,即:3Uo=Ua'+Ub'+Uc',三相电压对称平衡,开口三角绕组输出电压既3Uo=0 V。

索保锋,等 电压互感器开口三角接线的探讨 - 131

-

U'=0

UcB

Ub'

PT一次侧输入电压即为0,当一次系统三相电压不

十分平衡时, 由于辅助二次绕组接入的绕组数与理论要求的值100 V有出入,就会造成L点的电位偏

离地电位,造成开口三角形有不平衡输出,实际上,这个输出值不会很大,一般不超过3 V。

3Uo=Ua'+Ub'+Uc'=3Up

图2 A相接地时的向量

Fig.2 Vector diagram of single phase earthing

2 四只单相电压互感器构成的开口三角接线

当采用4只PT时,事情不再那么简单了: 1) 如果在原来三只PT基础上加装了与前三只相同的第四只

PT,二次接线如图3所示。

图4 第二种4PT接线二次回路原理图

Fig.4 The second kind of elementary secondary circuit of

4 single-phase voltage transformer

图3 4PT接线原理图

Fig.3 Elementary diagram of 4 single-phase voltage transformer

我们来分析一下:

3U0=UA+UB+UC=(Ua+Ul)+(Ub+Ul)+

(Uc+Ul)=Ua+Ub+Uc+3Ul

由此,就要求开口三角形接线正极性串接入第四只PT辅助二次绕组。并且第四只PT辅助二次绕组额定电压是原额定值的三倍,即100 V。

为了解决这个问题,现场作了如图4处理。 第四只PT辅助二次绕组额定电压是100/3 V,即33.3 V

V,即第四只PT二次绕组额定电压57.7 V。

即开口三角形接线正极性串接入第四只PT辅助二次绕组和第四只PT二次绕组,相当于串入第四只PT二次额定值为57.7+33.3=91 V的绕组,与理论要求的100 V比较接近。

在实际运行时,由于正常运行时,三相电压平衡,L点的电位与地电位相同(为0电位)第四只

当发生单相接地时,开口三角输出值不会因这种接线减少输出,此时,L点的电位处在接地相电压和地电位(0电位)之间。

假设接地情况为A相接地,假设两种极限情况: 一是假设L点电位为0电位,前三只PT电压三相对称,则式子3U0=UA+UB+UC=Ua+Ub+Uc+3U1中Ua+Ub+Uc=0。

第四只PT一次侧所加的电压为A相对地的电压。

3Uo=Ul=91 V

二是假设L点电位为A相电位,第4只PT电压输出为0,则式子

3U0=UA+UB+UC= Ua+Ub+Uc+3Ul中3Ul =0 这种假设其实忽略了第4只PT,3U0=UA+UB+UC= Ua+Ub+Uc=100 V

就是说,当发生单相接地时,3U0∈(91 V,100 V) 实际设备报接地故障的整定值一般为20~40 V,这种接线完全满足实际设备运行需要。

2) 如图5,这种接线,许多新参加继电保护工作的同志可能还一时接受不了,三只PT开口三角被短接,如果发生单相接地,这三只PT辅助二次绕组不就短路了吗?其实,当发生单相接地时,这三只PT辅助二次绕组中确实存在电流,但该电流不是很大,因为它只是将非故障相PT产生的电压加在故障相PT上,它只是将图3中L点的电位拉为中性电位(零电位)。由于地电位升高为单相电压,

- 132 - 电力系统保护与控制

加在第四只PT电压即为相电压。

此时,3Uo=Ul=100 V,

如果要满足以上条件,那么第四只PT的变比

。 3 另一种接线探讨

通过以上分析,可以得出另一种接线(图5)。

接线,就可以开口三角形接线正极性串接入第四只

PT辅助二次绕组,由于第四只PT辅助二次绕组额定电压为100 V,如图5所示能够满足

3U0=UA+UB+UC= Ua+Ub+Uc+3Ul

但在实际工程中,4只PT一般使用同一厂家、同一批出厂的同型号产品。故很少有四只PT变比不同的。所以这种接线在工程应用中很少见。

4 结语

[1] 梁之林,时朱大铭, 张英杰, 等. 两起GIS组合电器事

故原因分析及建议[J]. 电力设备, 2007(7):68-70.

LIANG Zhi-lin, ZHU Da-ming, ZHANG Ying-jie, et al. Case Study and Improving Suggestions for two Faults of GIS Switchgear Assembly[J]. Electrical Equipment, 2007 (7):68-70.

[2] IEC 60480-2004, Guidelines for the Checking and

Treatment of Sulfur Hexafluoride (SF6) Taken from Electrical Equipment and Specification for Its Re-use[S].

收稿日期:2008-12-01; 修回日期:2009-01-18 作者简介:

杜晓平(1978-),女,硕士,研究方向为电力系统调度自动化;

李 涛(1977-),男,硕士,研究方向为电力系统高压技术监督与设备维护;E-mail:[email protected]

陈瑞林(1975-),男,工程师,研究方向为电力系统技术管理与设备维护。


相关文章

  • 浅谈电压互感器开口电压
  • 浅谈电压互感器开口三角电压 摘要:电压互感器(PT)的开口三角电压回路对电力系统中的保护的正常运行起着重要作用,开口三角电压回路接线错误将会引起继电保护装置的误动作或拒动.本文分析了电压互感器(PT)在直接接地系统和非直接接地系统中,发生故 ...查看


  • 平衡绕组在变压器中的作用及接线方式浅述
  • 第46卷第12期2009年12月 变压器 刀酗N谨'DR^任漾 Vbl46December N0122009 平衡绕组在变压器中的作用及接线方式浅述 董景义,段玉柱,张贤国,马立明 (山东达驰电气有限公司,山东成武274200) 摘要:对平 ...查看


  • 电力电容器的保护原理及技术要求
  • 电力电容器保护原理技术要求 (1)电容器组应采用适当保护措施,如采用平衡或或采用瞬时作用过电流继电保护,对于3.15kV及以上的电容器,必须在每个电容器上装置单独的熔断器,熔断器的额定电流应按熔丝的特性和接通时的涌流来选定,一般为1.5倍电 ...查看


  • 电压互感器铁磁谐振的产生与消除
  • 第30卷第3期2010年3月 ElectricPowerAutomationEquipment 电力自动化设备 Vol.30No.3Mar.2010 电压互感器铁磁谐振的产生与消除 杨斌文,李文圣 (湖南文理学院电气工程系,湖南常德4150 ...查看


  • 电压互感器的工作原理
  • 电压互感器的工作原理与一般的变压器相同,仅在结构型式.所用材料.容量.误差范围等方面有所差别. 一.电压互感器: 电压互感器是一种电压变换装置.它将高电压变换为低电压,以便用低压量值反映高压量值的变化.因此,通过电压互感器可以直接用普通电气 ...查看


  • 电压互感器与消谐装置
  • 35kV电压互感器和消谐器的绝缘配合 张乃群 陈军 <高电压技术>1998年04期 消谐器 消谐器是保护电压互感器一次侧的阻尼器件,用来消谐电网中的谐振. 1消谐器用途 6-35kV中性点不接地电网中的电磁式电压互感器(以下简称 ...查看


  • 电容器保护中的不平衡电压和差压保护
  • 电容器保护中的不平衡电压和差压保护 电容器的差压保护就是电压差动保护,原理就象电路分析中串联电阻的分压原理.是通过检测同相电容器两串联段之间的电压,并作比较.当设备正常时,两段的容抗相等,各自电压相等,因此两者的压差为零.当某段出理故障时, ...查看


  • 电磁式电压互感器高压熔丝熔断的原因及处理方法
  • 电磁式电压互感器高压熔丝熔断的原因及处理方法 福建省南平市延平区埠湖水电工作站 张由桂 本文对引起电磁式互感器高压熔丝熔断的不同原因和处理方法作了分析, 向电气运行人员提出了在工作中应注意的事项. 根据笔者在樟湖水电工作站多年的设备检修与维 ...查看


  • 7RE2800电压闭锁继电器在小浪底水电站的应用
  • 7RE2800电压闭锁继电器在小浪底水电站的应用 一.概述 小浪底水电站6台容量为300MW的发电机于2001年底全部投入商业运行,投产机组全部接人河南电网,是河南电网的骨干调峰电站,它的安全运行对河南电网的安全稳定至关重要,其6台主变.发 ...查看


热门内容