基站空调维修手册

空调维修实用手册

空调维修实用手册

目录

一.基础理论··································································3 1. 制冷系统基本原理····························································3 2. 空调基本电源控制系统原理····················································3 3. 空调基本结构································································3 3.1. 压缩机····································································3 3.2. 冷凝器····································································4 3.3. 膨胀阀····································································4 3.4. 蒸发器····································································4 3.5. 控制面板···································································5 3.6. 控制变压器·································································5 3.7. 室外、内电机·······························································5 3.8. 三相接触器·································································6 3.9.电机电容·································································· 6

3.10.内风机继电器····························································· 6

4. 空调电机接线图······························································7 二.制冷工具使用操作方法·····················································10 1. 压力表操作方法·····························································10 2. 空调压力的测试和冲加制冷剂流程·············································10 3. 怎样连接管对制冷系统进行抽真空·············································11 4. 管工工具及使用方法·························································12 三.空调的日常维护要求······················································15 四.空调常见故障与分析······················································16 1.电源反相·································································16 2. 空调缺少 R22·······························································16 3. 空调 R22 过多······························································16 4. 空调压缩机故障····························································16 5. 节流阀(热力膨胀阀)故障··················································17 6. 空调室外风机故障··························································17 7. 空调控制面板故障··························································17 8. 空调交流接触器故障························································17 9. 空调变压器故障····························································17 10. 空调感温头故障···························································17 五.基站空调大至常见故障····················································18 1. 空调整机不工······························································18 2. 空调室内机转室外机不转····················································18 3. 空调器不制冷原因··························································18 4. 力博特空调室内机结冰原因··················································18 六.基站空调故障代码总汇····················································18 七.空调维修案例····························································22

1

空调维修实用手册

大金空调····································································22

案例 1:开机运转 25 分钟后整机停机且故障灯一直闪·····························22 格力空调·····································································22

案例 2:开机制冷 8 到 10 分种左右后出现 E1 告警································22 案例 3:格力整机无显示·······················································23

案例 4:室内机工作正常,室外机风扇运转,压缩不运转···························24 海尔三菱空调································································24

案例 5:正常制冷 5 到 10 分种后左右就不能制冷··································24 力博特空调··································································25

案例 6:室内室外机运行正常,但不能制冷,室外机储液灌烫手·····················25 案例 7:整机不工作,操作面板无反应···········································25 案例 8:高温告警, 室内机运行正常,室外机不工作································26 案例 9:空调启动运行后空气开关跳闸的现象·····································27 案例 10:空调控制面板按键失灵················································27 案例 11:空调内机正常运行外机不工作··········································27

案例 12:制冷效果差,内外机都正常,重启后能短时能制冷························28 三洋空调····································································28

案例 13:按“开/关键”开机,整机无反应,灯不亮······························28

案例 14:室内机工作正常,室外机不工作,开机几分钟后出现 E04 告警··············29 依米康空调···································································29 案例 15:开机制冷几分钟后,有 H1 告警·········································29 案例 16:整机不工作,操作面板无反应··········································30 依米康空调其它故障:··························································31 附:空调厂家电话·····························································32

2

空调维修实用手册

一.基础理论

1. 制冷系统基本原理

压缩机排出的高温高压气体经过冷凝器(室外机)通过风机把热量与空气中的介质进行 热交换散热(放热过程)后冷凝变为中温高压的液体制冷剂,然后通过膨胀阀或者毛细管进 行节流降压逐渐变为低压中温的制冷剂液体然后进入蒸发气(室内机)进行蒸发气化逐渐转 化为低温低压的气体,空气中的热量就被蒸发器所吸收,环境的温度就逐渐下降然后空气中 的水分就翻盖在蒸发器的表面上通过底部的接水盘排出室外(如下图)。

2. 空调基本电源控制系统原理:

室内配电箱三相四线引到室外机的接线端或交流接触器的输入端(注:输出端的电压主 要供给压缩机和室外风机使用)。从输入端引 220V 交流电压供室内机使用,经过室内稳压 器进行整流稳压后供给内机电脑板,再分 2 路电源,一路供给室内风机与控制面板、一路输 出低压控制信号,控制外机的低压部分(如三相接触器线圈的工作电压)控制交流接触器的 吸合与断开从而控制压缩机的启动与停止。 3. 空调基本结构 3.1. 压 缩 机

功 能:

1、(循环心脏)提高冷媒压力,以致冷媒可以在高温下冷凝,建立系统运作所需的两个 不同压力

3

2、促使冷媒在系统内流

空调维修实用手册

空调压缩机测量方法是测空调压缩机(380V )的三相阻值是否一样(约 5~9Ω),阻值

为零或差值大的可判断压缩机是坏的。阻值相近的一般情况下是正常的但不排出卡缸和串 气。空调压缩机(220V )的三相阻值是否是 A+B=C。

例: 压缩机三个功能脚的判断,用 RX 1 档测出阻值最大的两端,与这两端所对立的另一端 即为公共 C 端、然后以公共端 C 端为中心,测出其余两个脚的阻值,阻值大的那个脚为启动 S 端、阻值小的为 R 运行端。(C :为公公端、S :启动端、R :运行端) 3.2. 冷凝器

· 冷凝器——

经压缩后的高温高压气体较外面的冷却空气和水温度为高,所以能够将在蒸发器吸取的

蒸发潜热放出来,由冷却空气或水带走,本身却冷凝为液体,功能:把系统中的热放出。 3.3. 膨胀阀

—— 膨胀阀

控制冷媒流到蒸发器的流量,是冷媒由高压到低压差的分界点。当液体通过膨胀阀时,

压力突然降低,一部分液体会突然蒸发,称之闪蒸。闪蒸现象可把其余未蒸发的液体冷 却,变成冷液体。功能:调整冷媒的流量,起到节流、降压、降温的作用。

4

3.4. 蒸发器

空调维修实用手册

蒸发器——

冷媒液体一边流动一边蒸发,不断的吸收外面的热,变成低温气体。同时蒸发器外面的 空气或水便会被冷却。

3.5. 控制面板(参照:力博特、依米康)

作用:控制空调的启动与停止与参数的修改。

3.6. 控制变压器

作用:由交流 220V 电压转换为交流 12V 或者 24V 的低电压供电脑板使用。

空调变压器的测量方法:在带电测量的情况下,用万用表交流挡测量初级有 220V 输入,次

级有交流 24V (依米康、力博特)或交流 12V (其它机子如格力)输出。在断电常温下用万 用表欧姆挡(200Ω挡位)测量变压器的初级线圈阻值为 20Ω,次级线圈阻值为 0.04Ω.初级

5

空调维修实用手册

线圈的阻值比次级要大。 3.7. 室外、内电机

作用:起到加快冷凝器、蒸发器的散热、吸热的作用,强迫与空气进行热交换,加快冷凝、 蒸发的速度。

空调电机的测量方法:(380V )空调外风机三相阻值是否一样,为零的或阻值差距很大的可 判断是坏的,三相阻值相近的一般情况下是正常的,但不排除轴承损坏。(220V )空调内、 外风机三项阻值是否是 A+B=C。 3.8. 三相接触器

作用:交流接触器是利用电磁吸力,使电路接通和断开的一种自动控制电器 主要结构:主触点系统、辅助触点电磁系统、灭弧装置等几部分组成。

三相接触器的测量方法:(1)可以用万用表欧姆挡测量线圈阻值,一般为几百欧到几千 欧。(2)另外按下触点,用万用表测量对应上、下触点看相应的触点是否导通。 3.9.电机电容(符号:C )

作 用:启动作用

定义:凡是被绝缘物分开的两个导体的组合,就叫电容器。 电容的文字符号为:C

电容按极性分为:有极性电容、无极性电容 重要指标: 电容量(uF )、耐压值(380V/220V)

例如:35 uF、220V 表示:电容量为 35 uF、耐压值为 220V 并联电容器的总电容等于各个电容器的电容之和。即:C=C1+C2+C3

6

空调维修实用手册

测量电容方法:

1、可以使用“放电法”进行试验,即金属物体将电容器的两个接点短路,若电容能 正常放电,则说明该电容是好的。

2、用万用表(机械表)的两只表笔接触电容的两极,若表针先指低阻挡,并逐渐退 回高阻挡,表明电容器具用充放电能力,若表针指示在低阻值而不能退回时,表明该电 容已经已极间短路。若表针一开始就指示高阻值或表针不动,则表明已发生极间断路(即 电容器已经被击穿) 3.10.内风机继电器(力博特)

作用:控制室内风机的高低风速

圈正常阻值为 80 欧姆左右。 空调其它保护器:

测量内风机继电器方法:第一,在断电常温下使用万用表的欧姆挡测量 1、3 接线柱线

1、温度保护器,通常用于内风扇电机上,当风机出现堵转,过流、过热时,温度保护器断 开起到保护作用。温度保护器有两种形式,一种是当温度达到某一定值后就会永久性熔断, 这一类称为温度保险丝。另一种是当温度达到某一定值后,就会自动断开电路,当温度下降 到某一允许时,其自动会闭合,这一类称为温度保护开关。 2、 压力开关

压力开关的作用是,监测制冷设备系统中的冷凝高压和蒸发的低压压力值,当压力高于 或低于额定压力值时,压力开关断开,从而切断了控制回路的电源;或者将断开的信号反馈 到主控电脑板,再由电脑控制停机,从而起到保护的作用。

高压开关主要检测高压部分压力,只要低压低于限额度,低压开关就会断开。 好坏判断:高低压开关正常情况下都是导通状态,可用万用表电阻挡测量。 3、 过载保护器

过载保护器分为内置和外置式两种:

(1)内置式过载保护器装于压缩机(comp )里面,直接感受压缩机电机绕组的温度,检测 灵敏度较高。

(2)外置式过载保护器装在压缩机的接线盒内,开口端紧贴在压缩机的外壳上,随时感受 机壳温度,当电源接通时,如果电机不能正常运转,而出现电流过大,发热元件因电流过大 而升温,达到一定温度后自动切断电源回路,起到保护作用。如果压缩机外壳温度升高,同 样起到保护的作用。因此这种过载保护器具有过负荷和过温升双重保护功能。

好坏判断:用万用表电阻挡测量,它的两个接线柱在正常情况下是导通的,若阻值为无穷大, 则说明过载保护器已经损坏。 4.空调电机接线图

机型:力博特外风机接线图(2 版本、3 版本)

7

N

L

空调维修实用手册

L :火线 N :零线

机型:依米康(EDA81U )内风机接线图

Y/G:黄绿(接地) BK :黑色 BL :蓝色

R :红色

Y :黄色

LOW :低风速 M :中风速 HI :高风速 N :零线

8

空调维修实用手册

机型:依米康(EDA81USP )外风机接线图

N :零线

L :火线 BLUE :蓝色

BROWN :棕褐色

OR AND VERDANT:黄绿(接地) SWARTHY :黑色

H:高风速 C:电容 L:火线

M:中风速

L:低风速

S:最低风速

N:零线

9

空调维修实用手册

二.制冷工具使用操作方法

1.压力表操作方法:

一般现在的制冷行业中都是使用复合式双表来测量制冷系统的压力与充加冷剂、抽真空等

用途比较广泛,该表连接如下图。

首先说明几种单位值的换算——

压力单位值换算:

在工程技术中为了计算方便,把大气压力值取为 1kg/㎝² 来使用,在制冷技术中,常使用 兆帕(Mpa )为单位,在我们的压力表表盘上由里向外共有两圈数值刻度值,指出两种压力 数值。一种是英制表示(以 psi 表示)、一种是国际单位制表示(以 1kg/㎝²表示)。 它们之间的关系为:1kg/㎝²=9.8×10Pa=0.1 Mpa ≈ 1Kg ≈14psi 2.空调压力的测试和冲加制冷剂流程。 (1)空调压力的测试:

空调有高低压两个测试压力的工艺口,这两个工艺口和压力表高低压表口相对应接上 {压力表蓝色表管(低压表/真空表)接在空调的大管工艺口上(低压管);压力表红色表管 (高压表)接在空调的小管工艺口上(高压管)},接好后待空调压缩机启动,查看压力表 的压力变化,低压压力在 5~6kg(70~85psi)高压压力在 16~20kg(225~285 psi)是正常 的,压力过低的表明少制冷剂,压力过高的表明制冷剂充得过多。 (2)冲加制冷剂的流程:

空调冲加制冷剂时,将压力表高低压口接到空调高低压工艺口上,压力表中间管口连 接一根加氟管到制冷剂钢瓶上;再将压力表的高低压阀门打开,略扭松开制冷剂钢瓶阀门、 利用钢瓶自身制冷剂压力将压力表管内的空气排出。待空调压缩机启动后把压力表的高压阀

10

门(阀门 1)开关关闭,低压阀门(阀门 2)打开,随后完全打开钢瓶的阀门,制冷剂就会 随着压缩机吸收压力吸入空调制冷系统里;注意观察,待低压压力达到正常值时(正常值: 5~6kg(70~85psi)关掉低压阀门,同时也关闭制冷剂罐开关,观察空调运行 30 分钟压力 变化情况和空调制冷效果,压力都在正常值内,空调制冷正常,冲加制冷剂完成; 最后关机, 迅速扭出压力表高低压口,在用螺帽把空调高低压工艺口扭紧。请看图

3.怎样连接管对制冷系统进行抽真空?

请看下图:

如图所示,表中间连接嘴连接真空泵。

抽真空有三种方法:

(1) 低压单侧抽真空,直接将压力表蓝色表管(低压表/真空表)接在空调的大管工艺口

上(低压管),然后关闭红色表管(高压表)的高压阀门(阀门 1),然后启动真空 泵,随即打开低压阀门(阀门 2)进行抽真空,注意观察低压压力表的指针变化,

(2) 一般抽 30 分钟或指针指在-0.06Mpa 位置,将低压表的阀门关闭,在切断真空泵电

源。 (3) 高低压双侧抽真空 就是在空调高、低压管上的工艺口分别接上管然后进行抽真空。 (4) 复式抽真空

就是对整个制冷系统进行二次以上的抽真空,以获得理想的真空度,

经过一次抽真空后,制冷系统内部保持了一定的真空度。此时关闭高、低压表的阀 门,去掉真空泵接上冷剂钢瓶向系统内充注冷剂(一般充 1~2Kg 就可以了);启动 压缩机运转数分钟,使系统内残存的气体与制冷剂混合,再开启真空泵进行第二次 抽真空,抽空时间至少在 30 分钟以上,这样能使系统内的气体进一步减少,以达到 规定的真空度。这种方法比单侧抽真空效果好,但要损耗一定的冷剂量和时间。

4.管工工具及使用方法: (1)割管刀

割管刀也称为割管器,是专门切断紫铜管、铝管等金属管的工具。

割管刀的使用方法:将铜管放置在滚轮与割轮之间,铜管的侧壁贴紧两个滚轮的中 间位置,割轮的切口与铜管垂直夹紧。然后转动调整转柄,使割刀的切刃切入铜管 管壁随即均匀地将割刀整体环绕铜管旋转。如下图所示:

(2)扩管器

扩管器又称为涨管器。主要用来制作铜管的喇叭口和圆柱形口,扩管器的夹具分成对称 的两半,夹具的一端使用销子连接,另一端用紧固螺母和螺栓紧固。两半对合后形成的孔按 不同的管径制成螺纹状,目的是便于更紧的夹住铜管。

扩管器的使用方法:扩管时首先将铜管扩口端用锉刀锉修平整,然后把铜管放置于相应管径 的夹具孔中,拧紧夹具上的紧固螺母,将铜管牢牢夹死,具体的扩口操作方法如下图:

(3)硬钎焊(氧焊)

硬钎焊也称为氧焊,所需要的焊具为焊枪(焊炬)。所需要的焊接设备有氧气钢瓶、乙 炔气钢瓶(或液化石油气钢瓶)、连接软管及减压表等,使用的焊料为铜磷合金焊条(铜焊 条)。制冷管道的焊接我们一般采用钎焊焊接,意思就是通过可燃气体(液化石油气)和助 燃气体(乙炔)两者在焊炬中混合燃烧时产生的高温火焰,加热被焊材料,熔化焊料使之成 为间隙的充填金属,而使焊件连接,这种焊接方法就称为钎焊。 焊枪操作方法:

首先打开乙炔瓶的阀门开关、在打开氧气瓶的阀门开关,然后在焊枪处慢慢松开乙炔阀 门使得焊嘴有乙炔气体排出(注:记得不要开得过大),接着用打火机点着焊嘴使得乙炔气

体燃烧,再慢慢打开焊枪的氧气阀门(阀门 1 或阀门 2 都可以),调好火焰!在焊接前先对

焊口进行清洁,并且对焊口或管道进行预热,当铜管的颜色呈暗红色时立即将焊条放在焊接 处继续加热,直到焊条充分熔化流向间隙处,并牢固附在管道上时,移去火焰,焊接完毕。 然后先关闭焊枪的氧气阀门,再关闭乙炔阀门,最后关闭氧气、乙炔瓶阀门。要特别注意在 焊接毛细管与干燥过滤器的接口时,预热时间不能过长,焊接时间越短越好,以防止毛细管 加热过度而熔化。氧气过桥是大瓶氧气向小瓶加氧时提供的一种工具。

万用表:

万用表又叫万用电表或万能表,是一种使用极其广泛的具有多种用途和多个量程的直读式仪 表,它又分为指针式万用表与数字万用表。

一般的万用表可以测量直流电流、直流电压、交流电压和电阻等。目前使用比较广泛的是数 字万用表它测量精度高、输入阻抗高、显示直观、读数准确、功能齐全、体积小而且携带方 便等优点。从显示的灵敏度来讲,数字万用表又分有四位数字和五位数字。

数字万用表可测量电量有:直流电压、直流电流、交流电压、交流电流、电阻、电容、二极 管正向压降、三极管直流放大倍数等,有的表还附有交直流大电流(10A )测量各一档,还 具有自动调零和显示极性的功能、超量程和电池低电压显示功能。 钳形电流表:

钳形电流表又称卡表,用于测量交流电流。 钳形电流表使用注意事项:

1、为使读数准确,钳口的两表面应紧密闭合

2、进行电流测量时,被测载流导线的位置应放在钳口中间,以免产生误差。

3、测量前应进行估计一下被测电流的数值范围,选择合适的量程,或先选用较大的量程测 量,然后再视电流的大小选择适当的量程。

4、若要测量较小的电流时,可将导线在钳形铁芯上绕几圈,这时,指针便停留在较大电流 的数值上。把测得的电流值除以绕在钳形铁芯上的导线匝数,即是该导线的电流值。

(图:钳形电流表)

使用万用表欧姆档分别测量压缩机的三个功能脚线圈阻值(CS 、RS 、CR ),应无开路或者 短路的现象,并且不会对地短路。如下图演示:

青岛海尔 KFR-75LW/D(JZ )的停电补偿设定方法:

作用:设定停电补偿功能后,整机运行过程中突然停电,再次恢复供电时,则整机恢复原来

工作状态。

设定方法:在空调内机接通电源正常开机的状态下,5 秒钟内连续按遥控器睡眠键 10 次, 蜂鸣器响 4 声后进入停电补偿状态。

取消方法:5 秒钟内连续按遥控器睡眠键 10 次,蜂鸣器响 2 声后取消停电补偿功能。

三.空调的日常维护要求

机房的空调是否能正常工作,日常维护是非常重要的!并且机房空调是维持机房内一定 温度、保证其它通信设备正常工作的,它对机房起到降温、除湿的作用。所以维护人员应该 做到以下几点:

1、在日常巡检中,注意查看空调内外机是否工作正常!是否制冷,内机显示面板有无显示。 2、显示面板有无告警

3、用万用表测量电源电压三相 380V±10% ,单相 220V±10% 4、空调专线应承受空调额定电流的 1.5 倍。

5、清洗空调内机过滤网、用清洗剂全面清洗外机冷凝器翅片,并且清除挡住冷凝器出风口 物体。

6、用抹布清洁空调室内机表面,清理空调内机过滤网里面风机底部的杂物。 7、检查室内、室外电机是否运转而且固定脚是否牢固有无松动之类。

8、查看室内配电箱中的空调电源线是否老化、发热、接线是否有松动、脱落、地线接地是 否牢固。

9、查看控制面板设定的温度、湿度是否正确(温度 25℃、湿度 60%左右)

10、测量压缩机运行电流及绕组对地绝缘阻值,紧固接线螺丝,检查压缩机的运行噪声和机 身温度是否正常、测量吸、排气压力。

11、注意倾听压缩机的运行声音,有无反转的现象(反转就是反相,故障现象是压缩机嗡嗡 响或者震动很厉害,正常运转下是比较安静的) 12、检查空调有无来电自启功能。

13、当发现有空调故障并且解决不了时,一定要现场反映给项目的空调主管,寻求技术支持, 同时也方便做好故障维修记录。

14、输通机内、给排水管路,更换破损的保温套

15、现场与机房 BSC 核对空调移位、压力告警是否正常,各接线端子是否牢固而且贴有标 签。

16、检查相关控制、电气部分,包括空气开关,接触器等。

17、检查管路各骡纹接口、焊接口有无油迹(一般情况下泄漏处都会有油迹).

四.空调常见故障与分析

1.电源反相

压缩机无排气与吸气压力,没有温差 空调室内和室外机都启动,但不制冷。 解决方法;换相 2. 空调缺少 R22

(1)空调整机运行内机吹出的风不够冷。 (2)空调整机运行外机吹出的风不热。 (3)空调整机频繁启动运行。 (4)出现高温高压报警。 (5)出现低压保护告警。 (6)管路出现结霜现象。 解决方法:冲加制冷剂。 3.空调 R22 过多

(1)空调整机运行不制冷。

(2)会出现高压保护。(外机不工作,内机正常工作) 解决方法:排出多余的制冷剂。 4.空调压缩机故障

(1)空调压缩机烧坏或被电击穿。

(2)空调压缩机卡缸或串气。 (3)空调压缩机运行声音异常。 解决方法:更换压缩机。

空调压缩机测量方法是测空调压缩机(380V )的三相阻值是否一样(约 5~9Ω),阻值 为零或差值大的可判断压缩机是坏的。阻值相近的一般情况下是正常的但不排出卡缸和串 气。空调压缩机(220V )的三相阻值是否是 A+B=C。 5.节流阀(热力膨胀阀)故障 (1)空调运行后不久停机保护。 (2)热力膨胀阀前后管路温差大。 (3)空调制冷效果不好或不制冷。 (4)空调高低压力异常。

解决方法:调节热力膨胀阀开关或更换热力膨胀阀。 6. 空调室外风机故障

(1)空调运行后不久停机保护。 (2)出现高温告警。

(3)空调制冷效果不好或不制冷。

(4)空调外风机的电容损坏也会导致风机的正常运行。 (5)空调外风机运行时的声音异常。 解决方法:更换外风机或外风机电容。

外风机好坏的判断方法是。(380V )空调外风机三相阻值是否一样,为零的或阻值差距很大 的可判断是坏的,三相阻值但不排除相近的一般情况下是正常的,但不排除轴承损坏 。 (220V )空调外风机三项阻值是否是 A+B=C。 7. 空调控制面板故障

(1)空调控制面板无显示或无法操作。 (2)空调停电后无法自起。 (3)空调室内机启动外机不启动。

(4)空调控制面板内有无损坏(保险烧坏,电阻爆裂等) 解决方法:更换空调控制面板。 8. 空调交流接触器故障

(1)空调整机不工作(依米康有这样的现象)。 (2)空调内机工作外机不工作。

(3)空调内机工作外风机工作但压缩机不工作。(交流接触器可能有一或两个触点坏。) 解决方法:更换交流接触器。

交流接触器的判断好坏是,有交流电压 24V 或交流 220V (空调大多是用 24V 的如力博特, 依米康等,用 220V 是格力、松下等国产空调)到交流接触器线圈,如交流接触器不吸合可 判断已坏:如吸合但运行不正常,可测试交流接触器的每组触点是否正常来判断其好坏。 9. 空调变压器故障 空调整机不工作。

解决方法:更换空调内机变压器。

空调变压器的检测方法是用万用表测试空调变压器的初级和次级有无电阻,无电阻可判断已 坏。

10. 空调感温头故障

(1)室内感温头坏,可能出现无法感温不能控温或外机不启动。 (2)室外感温头坏,可能出现外机不启动。

(3)空调不会自停。 解决方法:更换感温头。

感温头好坏的判断是测量其电阻是否正常(5KB 和 15KB )。

五.基站空调大至常见故障

1.空调整机不工作

(1)外部电源故障(如空调电源空开有问题或电源线断路)。 (2)变压器烧坏

(3)室内机电脑板故障(保险管和压敏电阻烧坏) (4)控制面板故障

2.空调室内机转室外机不转

(1)室内机没有通讯信号输送给室外机(室内机电脑板没有信号输出给室外机) (2)室外机交流接触器坏不吸合,压缩机和室外风机得不到电源。 (3)氟多或氟少,引起高压保护开关动作或压缩机过热保护。 (4)室外机冷凝器过脏保护 (5)室外机电脑板故障

(6)室外压缩机烧坏或室外风机烧坏 3.空调器不制冷原因

(1)外部电源故障(如空调电源空开有问题或电源线断路三相错相)。 (2)室内机无压缩机信号输出

(3)室外机保护开关动作(如高、低压保护开关动作,室外机不运转,冷凝器过脏) (4)压缩机接线问题或压缩机故障。 (5)室外机交流接触器坏

(6)室外板故障或室外相序保护器坏

(7)氟多或氟少,引起高压保护开关动作或压缩机过热保护。 4.力博特空调室内机结冰原因

(1)室内风机不运转(启动电容坏或室内风机坏)

(2)室外机交流接触器吸合后沾死,达到设定温度也不能跳开,压缩机常时间运转不停。 (3)2 板本室内温度板坏,3 板本室内线控板坏。

六.基站空调故障代码总汇

空调型号:依米康(EDA81U 、EDA81USP )

1、“H1”——高压保护(冷剂多、室外机过脏、压缩机的电流值>3.5A、室外风机不运转) 2、“L1”——低压保护(冷剂少的原因引起或者系统堵塞) 3、“FIA ”——高温、高压报警(冷剂少) 4、“HT ”——高温报警

5、“FLA ”——风量丢失(过滤网脏、内风机不转或者转速变慢) 6、“HA ”——高温报警(室内温度超出 30℃)

空调型号:力博特(DME027-PWC2、DME027-PWC3)

1、 HIGH TEMPERATURE ALARM——高温报警(室内回流空气温度升高至高温报警设

定值;需重新设定高温报警值)

2、 LOW TEMPERATURE ALARM——低温报警(室内回流空气温度降低至低温报警设定

值;需重新设定低温报警值)

3、 LOSS OF AIR FLOW——气流量低(把风速调为高速就可以解决)

4、 室内风机不运转——(1)室内风机继电器线圈烧坏,更换继电器或者临时短接。(2)

内风机的线圈烧坏,正常阻值为 100 欧姆以上

5、 室外风机线圈烧坏导致空调不制冷,正常正常阻值为 100 欧姆以上 6、 室外机的保险丝烧坏

7、 空调室外机不工作!无 24V 控制电压输出给外机!内机接口板烧坏更换内机接口板 8、 空调反相!故障现象:压缩机无排气与吸气压力没有温差,压缩机很响有嗡嗡的声音!

解决方法就是换相。 9、 控制变压器线圈烧坏

海尔(LF73WDT 、KFR-71LW/(JZ ):

1、 到目前只发现一种故障,空调显示“E40”是市电电压不稳定造成(缺相或者电压过高),

重新启动空调就可以恢复制冷。

2、 不能自起(自起功能失去作用)或者其它故障。

3、 空调反相(现象:控制面板可以显示而且是在制冷(﹡)的模式下,外风机也运转;但

空调出风口不冷)换相。 格力空调故障代码:

三菱海尔重工故障代码

三菱电机空调 PSH 系列空调故障代码灯:

室外机 LED 故障灯: LED1 相序接反 LED2 缺相

LED3 室外传感器异常 LED4 63H2 功能(传感器) LED5 51C 功能(压力开关) LED6 26C 功能(压力开关) LED7 过热保护

LED8 控制输入电路异常

松下空调故障代码:

大连三洋空调机常见的故障代码及处理方法

7 8 9 10 11 12 13 4 5

P02

无冷剂引起压缩机热保护

雷击或高电压而引起外机电路板或变压 器烧坏(或室内外机相连的控制线路故 障)

内机检测到遥控器或机组控制的异常信 号

串行信号的发送故障 串行信号的接收故障

室内机组的型号与室外机组不匹配 室内机组的容量码没有设定 室内机组型号设定错误(容量) 不能探测室内机侧热交换器温度 不能探测室内机侧热交换器温度

检查是否有泄漏点, 处理后抽空, 加制冷剂 更换室外机电路板或变压器(检查控制线 路)

E04

6 E03 E02 E01 L02 L09 L13 F01 F02

控制线路被干扰, 检查干扰源, 断电重起. 检查控制线路部份 检查控制线路部份

重设室外机型号(地址码开关) 设定室内机容量码 重设室内机型号(容量) 检查室内机感温包(E1=TH2) 检查室内机感温包(E2=TH3)

一般是室外机散热器赃堵或散热不好, 检 查室外机排气感温包(PC 压缩=THOA) 检查室外机感温包(C1=THOE) 检查室外机感温包(C2=THOC) 检查压缩机工况

检查压缩机转子工况(一般情况是卡住) 检查电源相序各接触点是否良好 检查制冷剂是否不足

14

F04

不能探测排气温度

15 16 17 18 19 20

F06 F07 H01 H02 H03 H06

不能探测室外热交换器的液体温度 不能探测室外热交换器的气体温度 PC 压缩机用电动机过载 PC 压缩机用电动机锁定 压缩机的电流检查电路异常 低压开关

七.空调维修案例 大金空调

案例 1: 故障现象:

开机制冷,运转 25 分钟后,整机停机,故障灯一直闪。 问题:

管温热敏电阻变值 故障分析:

1、连接线接触不良 2、市电电压不稳定 3、管温热敏电阻变值 故障检测排除:

开机运转,制冷也正常。但过了 20 分钟以后,未达到设定温度就停机,故障灯一直闪。 检查市电和连接线均无发现有问题,用 202K Ω挡测量室内管温热敏电阻发现阻值才有 2K Ω (常温下正常值应在 5—10K Ω),开机一段时间后,导致控制板误动作。 处理过程:

更换上好的室内管温热敏电阻,试机正常。

格力空调

案例 2:

故障现象:

格力 KF-72LW(72332)-R-N5 开机制冷 8 到 10 分种左右后出现 E1 告警, E1 告警是格 力空调其中的故障代码(压缩机电流过大保护,压缩机过热保护,室外机排气温度过高保护, 室外机相序电流保护电路板坏)。重新断电开机后故障现象一样。 问题:

室外机积太多尘土,太脏倒至空调过热保护 故障分析:

在这就把格力 KF-72LW(72332)-R-N5 机型出现 E1 告警所有问题全部列出: 1、氟利昂多引起高压保护器动作(断开)。

2、该机使用的时间过长,制冷系统内部有泄漏处理完后常加冷剂或更换过压缩机不注意, 脏物入进制冷系统引起毛细管堵塞不能达到节流、降温、降压作用。倒至空调器高压压力过 高、低压压力过低,压力保护器动作(断开)。

3、室外风机坏(注:风机启动电容坏,风机也是不动转),不转,倒至保护器动作(断开)。 4、室外机相序电流保护电路板坏

5、室外机凝器积太多尘土、太脏倒至空调过热保护 故障检测排除:

经过检测,空调器制冷时用压力表测量低压压力过高为 0.75 Mpa(0.5~0.6 Mpa),停机后 平衡压力为 0.9Mpa (表示系统里氟利昂不多不少)。该机使用的时间只有一年,并且没有更 换过压缩机,空调器制冷时用压力表测量低压压力为 0.75 Mpa 不是负压状态,可以排除毛 细管堵塞的可能。空调器制冷时直观室内风机和室外风机都正常运行,可以排除风机坏的可 能。如果是室外机相序电流保护电路板坏,空调器室内机运行 3 到 5 分钟后,室内机电脑 板输送信号给室外机相序电流保护电路板时就马上出现 E1 告警,空调器是不能够制冷的。 由此可见,只有室外机凝器积太多尘土、太脏倒至空调过热保护出现 E1 告警。 处理过程:

清洗干净空调室外机冷凝器,试机正常,故障处理完毕!

注:1、发现 E1 告警,又不是室外机过脏过热保护时,最大的可能原因是室外机相序电流 保护电路板坏,在没有配件更换的情况下,我们可以临时跳开不用。方法:打开室内机底下 面盖,在打开室内机风机顶上的铁皮盖就可以看到室内机电脑板上有一根黄色电源线(标有 OVC 字母,这根线就是保护线),找一根电源线从室内机零线接好引到这根黄色线上(在电 脑板上不能取肖它,照常接好,只是多引一根零线和它串连),连接好后空调就能够制冷正 常,如果还是不能够制冷说明室外机保护继电器坏。

注:2、到了基站我们发现格力室内和室外机都运行正常,又是在制冷模试状态下,空调不 能制冷时,原因是空调器三相错相,更换好相序即可制冷。 案例 3: 故障现象:

格力 KF-72LW(72332)-R-N5 整机无显示 问题:

室内机变压器烧坏 故障分析:

基站格力空调室内机是由交流市电 220 伏供给,220 伏经过压敏电阻和保险丝在到变压器初 级变压后次级为 AC12~14V 左右输出供给室内电脑板使用。由此我们可以分析为: 1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、变压器烧坏或室内机电脑板上的保险、压敏电阻(ZNR )烧坏。 3、室内机电脑板上的稳压元件 7812 或 7805 损坏。

4、操作板故障(如接线松动或按键损坏) 故障检测排除:

按“开/关键”开机,整机无反应。打开室内机接线盒,检查接线端子已有市电 220±10% 电压输入。再检查室内机电脑板上的保险丝和压敏电阻均良好,再测量检查变压器的初级有 AC220V ,次级没有有 AC12~14V 左右输出,正明变压器已烧坏。 处理过程:

更换上好的变压器,试机正常。 案例 4: 故障现象:

格力 KF-72LW(72332)-R-N5 室内机工作正常,室外机风扇运转,压缩不运转。 问题:

室外机三相保护器坏 故障分析:

1、室内机工作正常,室外机风扇也运转(说明室内机没有故障,已有信号输送到室外机) 2、室外机故障:一、压缩机坏。二、市区电缺相。三、压缩机交流接触器坏。四、三相保 护器坏。 故障检测排除:

室内机工作正常,室外机风扇也运转(说明室内机没有故障),打开室外机则盖发现压缩机 不工作。测量市电已有 380V 电压到室外机,在测量三相保护器上的接线触点发现(A 点与 零线测量有 220V ,但是 C 点与零线测量没有 220V ,正明三相保护器已坏) 处理过程:

更换上好的三相保护器,试机正常。

海尔三菱空调

案例 5: 故障现象:

海尔三菱重工 3 匹机,室外机空调连接铜管被盗,重新焊接好连接管,抽真空加氟利昂,开 机前 3 分钟后,室内机和室外机运行正常,每次重新开机都只能正常制冷 5 到 10 分种后左 右就不能制冷。 问题:

空调制冷系统冰堵 故障分析:

1、 查三相供电电压是否正常,三相接线端子是否都接稳接捞。因为空调压缩机启动时电流

比较大,如果电压不稳定,接线接触不良,电流会不断慢慢增大,倒至电流保护或压缩 机热保护。

2、 室内和室外机通信是否正常。海尔三菱重工重新开机后 3 到 5 分钟,从室内机电脑板输

送信号给室外机,室外机才能够得到信号正常运行。

3、 空调分为两大系统(控制电器系统和制冷系统)。空调器的高、低压保护器是否动作,

充加氟利昂时是否加多或加少。 故障检测排除:

1、 经测量三相供电电压都很正常(380V±10%),三相接线端子接线也很捞固。由此可以排

除电压不稳定问题。

2、 开机 3 分钟后,室内室外机运行正常,能够正常制冷 5 到 10 分种才不能制冷。由此可

见,可以排除内外机通信信号异常的可能。

3、 制冷几分钟后,空调压力保护器动作(断开)。在空调还能够正常运行时,用压力表 量空调压力:高压压力特别高,低压压力在从正常制冷时的 0.5Mpa ,运行几分钟后缓慢变 小,最后到负压,空调保护器动作停机,停机 15 到 20 分钟后平衡压力逐步慢慢回升至 0.9Mpa 左右(表示氟利昂充加不多不少)。经过逐步分析到这,就可以找到故障的原因:由于该机 室外铜管被盗,压缩机吸入大量潮湿空气或大量水份,致使制冷系统里积存了大量的水分, 当焊接好连接铜管抽真空充注好氟利昂后,空调机制冷工作时,水分和氟利昂混合在一起, 经过压缩机高压排气到毛细管:节流、降温、降压后,水份结成冰,堵塞毛细管,使空调器 制冷系统不能够组成制冷巡环的过程。本机工作情况明显是冰堵。 处理过程:

放掉制冷系统中的氟利昂,在高压管截流毛细管前端加焊一个能够扭开放出硅胶的干燥 硅胶过滤器,重新抽真空加冷剂。其后第一次开机运行 15 分钟左右收氟关机,打开干燥硅 胶过滤器,把里面由原来的蓝色硅胶变成变白色硅胶放出来,重新在加入硅胶,扭好,排空 气在运行,第二次运行 30 分种左右,在放出变为白色的硅胶。以此操作 3 到 4 次左右,直 到放进去的硅胶在也不会变面白色(表明制冷系统里面已不在有水份)。收好氟后,即可将 过滤器拆除,重新焊接好铜管,排室内机管道里的空气,试机 30 分钟制冷正常。故障处理 完毕!

力博特空调

案例 6: 故障现象:

力博特空调室内室外机运行正常,但不能制冷,停机重新开机后有时又能制冷一下,到现场 用手摸室外机储液灌感觉很烫手。 问题:

室外机平衡阀坏,有时串气引起制冷系统流向错,制冷系统不经过室内机蒸发器循环,倒至 不能够达到制冷系统 4 大件循环的目的。 故障分析:

室内室外机启动正常,但不制冷,由此可以考虑到空调器电器部分没有问题,只有检测制冷 系统部分: 1、氟利昂多或少。

2、热力膨胀阀坏,不能达到节流、降温、降压作用。

3、电磁阀坏或室外机冷凝器灰尘积多过脏, 引起室外机保护继电器动作(断开)。 4、室外机平衡阀坏, 引起制冷系统流向错 故障检测排除:

经过检测,用压力表测量制冷系统停机平衡压力为 0.9Mpa (表示系统里氟利昂不多不 少),检查室外机保护继电器是否动作(断开)都为正常(表示电磁阀正常,室外机冷凝器 没有因灰尘积多过脏),当时以为是电压相序错,调相序后一样不能够制冷, 最后用手摸储液 灌感觉很烫手,正常时储液器不是烫手反而有点冰凉,由此可以断定是室外机平衡阀串气, 冷剂经过压缩机吸收压缩后排出的高温高压气体冷剂流向冷凝后直接循环回储液灌到压缩 机,冷剂没有循环到室内机蒸发器和热力膨胀,所以达不到空调 4 大件制冷系统循环的目的。 处理过程:

将系统内冷剂全部放空,焊出平衡阀不用,不会影响制冷效果(此阀的主要作用是保证 流经冷凝器内的冷媒量保持稳定,其实现在的定频压缩机在额定工况下输出冷媒量是比较稳 定,所以此阀可以不用),重新连接焊好制冷系统回路,抽空加氟利昂,开机制冷正常。故 障处理完毕!

案例 7: 故障现象:

力博特空调整机不工作,操作面板无反应。 问题: 变压器烧坏 故障分析:

在这我就不针对变压器单一问题来分析,把力博特空调(2 板本和 3 板本)从室内到室外机 整个电器控制系统一一分析:

1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、(室内机部分)变压器烧坏。

3、(室内机部分)变压器次级输出端保护开关动作(断开) 4、(室内机部分)电源接口板烧坏 5、(室内机部分)风机继电器烧坏 6、(室外机部分)保护继电器动作 7、(室外机部分)交流接触烧坏 故障检测排除:

力博特空调通常接线:380 伏电压从空气开关直接接到室外机交流接触器输放端(注: 也有少部分力博特空调是 220V 的,从空开接 220V 电压到力博特空调室外机交流接触器输 入端的,该机为 220V 压缩机),室内机另从空开供给 220V 电压。整机不工作,操作面板无 反应:1、测量是否有市电或缺相断路,正常。2、测量变压器初级有 220V 交流输入,次级 是否有交流 AC24V 左右输出,有表示变压器完好,无 AC24V 输出表示变压器烧坏。3、变 压器次级输出端保护开关是否动作,如动作,重新按回去即可(它的作用是:电压电流过大 时,动作断开保护后面的电路断开)。4、变压器次级有 24V 左右电压输出,正级接入电源 接口板,另一根(白色)接机壳。测量风机继电器线圈(面对机子,风机继电器最低部那两 根)1 口和 3 口有 AC24V 左右电压和测量室内机连到室外机的接线端子 1、2、3 号线(棕、 红、橙)端子,1 号和 2 号线或 1 号和 3 号线有 24V 左右交流电输出(表示电源接口板已有 信号输出,电源接口板无故障)。5、测量风机继电器线圈 1 口和 3 口有 AC24V 左右电压, 再测量面对风机继电器最左上角的端子和 220V 零线是否有 220V 电压,有表示这个继电器 完好,无表示继电器坏室内风机不运转。6、室外机保护继电器到目前还没有发现坏过,它 的作用是:制冷系统压力过高保护,电压电流过大保护。正常制冷时,它是由室内机接线端 子 1、2、号线(棕、红)输入 24V 电压,再由这个保护继电器来控制室外机的交流接触器 线圈。有时发现空调器能制冷几分钟后,室外机不运转,就是这个保护继电器动作,这时测 量不是 1 号和 2 号线(棕、红)有 24V 电压,反是 1 号和 3 号线(棕、3 号橙色是保护线) 有 24V 电压。1 号和 3 号线有 24V 电压,表示制冷系统压力过高保护,可能的原因有:室 外风机不运转,氟利昂多,室外机冷凝器过脏,电磁阀不吸合。7、室外交流接触器是控制 压缩机和室外风机供电启动的重要元器件,交流接触烧坏,室外机整机不工作。测量方法: 只要交流接触器线圈有 AC24V 电压,交流接触又能吸合正常(表示交流接触器完好 ),测 量线圈有 AC24V 电压,但交流接触又不能吸合(表示交流接触器线圈已烧坏,已不能在使 用)。 处理过程:

测量有交流市电 220V 电压到空调室内机。再测量变压器初级有 220V 交流输入,测量变压 器次级无交流 24V 输出(表示变压器烧坏),更换新的变压器,开机制冷正常。故障处理完 毕! 案例 8:

力博特空调高温告警, 室内机运行正常. 室外机不能工作 问题:

室外机三相交流接触器坏,导致室外机不能工作 故障分析:

力博特空调高温告警, 室内机运行正常,室内机运行正常,室外机不能工作。有制冷式 COOL. 但不能制冷。 可能原因有:

1:内机接口板坏,没有 24V 电压送给外机保护继电器

2:保护继电器坏,没有 24V 电压送给室外机三相交流接触器坏 3:室外机三相交流接触器坏,室外风扇电机和压缩机没得到市区电。 故障检测排除:

用万用表来测量,室外机三相交流接触器线圈已获有交流 24V 电压(表明内机接口板和外 机保护继电器是完好的),交流接触器线圈已获有交流 24V 电压但外机三相交流接触器伋不 吸合。断电用电阻档量三相交流接触器线圈无穷大。这时证明三相交流接触器线圈已烧坏, 更换三相交流接触器,试机正常。 处理过程:

更换三相交流接触器,试机正常。 案例 9: 故障现象:

力博特空调启动运行后空气开关跳闸的现象。 故障分析:

空调电源部分有对地或配件短路。 处理办法:

首先关电,再用万用表(欧姆挡)开始从空调电源线路开始检查或选择性的排查。

其次检查看线路有没有短路或对地。空调线路短路主要是注意线和线之间有没有短路或空调 配件烧坏造成内部短路,线路短路主要是电路板和一些保险装置损坏;空调线路对地主要检 查火线是否有直接对地的或配件烧坏后导致对地的,线路对地主要是火线和压缩机、内外风 机绕阻损坏对地。

检查出故障点后,整改线路或更换损坏配件,最后开机试机查看是否恢复。 案例 10: 故障现象:

力博特空调控制面板按键失灵现象。 可能有的故障:

空调控制面板坏或低压电压异常。 处理办法:

首先检测电源部分的低压部分供电是否正常(主要是空调内机变压器的好坏),变压器使用 24V 。检测办法是用万用表(200 殴)检测,线圈的阻值(初级是 13 左右殴、次级 6 殴这样 左右),超出范围或无限的可判断已坏。也可以带电测量,用万用表电压档检测查看有没有 24V 输出,有 24V 输出表示正常,如超出范围表示已损坏。

其次空调低压部分正常,就可能是电路板坏,主要是检电路板的保险部分是否完好和输出给 控制面板的直流 5V (N5 和 T 口电压)否正常来判断。

检查出故障点后,更换损坏的控制面板配件,最后开机试机查看是否恢复。 案例 11:

力博特空调内机正常运行外机不工作。 可能有的故障: 1、电路板故障。 2、元件故障。 3、系统故障。 处理办法: 电路故障。

外机到电的启动过程。

(市电 380V 外机同时引 220V 到内机,内机的 220V 通过变压器后输出 24V 交流低压给 电路板检测,检测后的 24V 提供给外机的交流接触器工作,交流接触器工作后外机启动运 行) 根据启动过程一路排查元件和线路的好坏排查。

首先检测市电是否正常(线电压 380V 左右,相电压 220V 左右),在市电正常情况下停 电用万用表欧姆档检测空调电路,先检测电源部分的低压部分供电是否正常(主要是空调内 机变压器的好坏),变压器使用 24V 。检测办法是用万用表(200 殴)检测,线圈的阻值(初 级是 13 左右殴、次级 6 殴这样左右),超出范围或无限的可判断已坏。也可以带电测量,用 万用表电压档检测查看有没有 24V 输出,有 24V 输出表示正常,如超出范围表示已损坏。 变压器输出 24V 通过室内电路板检测后,传到外机交流接触器,如无输出就可能是电路板 坏,电路板检测主要是检电路板的保险部分是否完好和输出给控制面板的直流 5V (N5 和 T 口电压)否正常来判断。有 24V 到外机后还有检测交流接触器好坏(交流接触器主要检查 线圈电阻是否在 6 殴左右和触电的好坏)才检测完线路和元件。 系统故障。

(系统压力过低或过高,低压保护开关和高压保护开关动作保护空调,外机不启动或启 动平凡)

检测办法首先用压力表检测系统静压压力,正常的静压在九到十公斤左右,如果低于表 示压力过低,需充加制冷剂,如过高排出制冷剂。 案例 12: 故障现象:

力博特制冷效果差,内外机都正常,重启后能短时能制冷。 可能存在问题: 1、 平衡阀故障。 2、 膨胀阀问题。 处理办法:

1、平衡阀主要平衡压力的,损坏后制冷剂不通过蒸发器循环,空调不能制冷,需更换平衡 阀。

2、膨胀阀在系统中主要是节流降压作用,膨胀阀坏系统可能出现堵塞,出现系统压力参数 改变,制冷效果差或不制冷。出现的现象有膨胀阀前后的温差很大或系统高低压压力高压偏 高低压偏低。修复需要更换膨胀阀。

三洋空调

案例 13: 故障现象:

三洋 SPW-V253DHL5 机型,按“开/关键”开机,整机无反应,灯不亮。 故障分析:

1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、变压器烧坏或室内机电脑板上的保险、压敏电阻(ZNR )烧坏。 3、室内机电脑板上的稳压元件 7812 或 7805 损坏。 4、操作板故障(如接线松动或按键损坏) 故障检测排除:

按“开/关键”开机,整机无反应。检查接线端子空气开关是有市电 380V ±10%电压输入。 有,再检查室内机电脑板,保险丝和压敏电阻均良好,再测量检查变压器的初级有(AC 代 表交流电压)AC220V ,次级有 AC12~14V 左右输出,正明变压器正常。再检查电脑板的 稳压元件 7812 或 7805,7812 没有+12V 输出,说明电脑板故障。 处理过程:

申请室内电脑板更换,试机正常,故障处理完毕!

注:1、如果直观看到室内机电脑板保险、压敏电阻(ZNR )烧坏,我们在断开电源空开下 可以临时小心撇断压敏电阻(ZNR ),更换上好的保险,开机,试机正常运行。 案例 14: 故障现象:

三洋 SPW-V253DHL5 机型,室内机工作正常,室外机不工作,开机几分钟后出现 E04 告警。 问题:

室外机电脑板上的保险和压敏电阻(ZNR )烧坏。 故障分析:

1、室内机没有信号输送到室外机或室内室外机连接线故障。

2、室外变压器烧坏或室外机电脑板故障或室外机电脑板上的保险和压敏电阻(ZNR )烧坏。 故障检测排除:

打开检查室内机电脑板,没有发现有烧坏的元器件。开机几分种后,测量室内机接线端子的 信号线输出正常(说明室内机没有故障)。打开室外机的则盖发现室外机电脑板上的保险和 压敏电阻(ZNR )都烧黒(说明保险和压敏电阻已烧坏需要更换)。同时我们要测量一下室 外机变压器是否完好,因为有时保险和压敏电阻烧坏时,变压器同时也会烧坏。测量变压器 方法:断电 200Ω挡测量初级通常会比次级大 10 倍以上(说明是好的)。 处理过程:

断开电源空开,临时小心撇断压敏电阻(ZNR )不要,更换上好的保险,开机,试机正常运 行。工具包带有压敏电阻,最好也要更换上好的压敏电阻,这样能够更好的保护室外机电脑 板。或更换新的室外机电脑板。

依米康空调

案例 15: 故障现象:

依米康空调 EDA81U 开机制冷几分钟后,有 H1 告警。 问题:热力鼓胀阀坏。

热力膨胀阀是制冷系统中重要的截流设备,它工作的正常与否直接关系到制冷系统制冷的效 果。工作原理:通过感温包感受蒸发器出口处铜管温度的变化,导致感温系统内产生不同的 压力,使传动膜片(波纹管)形成上下位移,并将此传递给传动杆从而推动阀针上下移动, 使阀门关小或开大,起到节流、降温、降压作用。膨胀阀通常是不能完全关闭的。膨胀阀阀 芯的行程一般不超过 6MM ,但也与膨胀阀的规格大小有关。 故障分析:

“H1”——高压保护(冷剂多、室外机过脏、压缩机的电流值>3.5A、室外风机不运转)

1、外部电路电压不稳定(高或低),电流值过大,正常测量电压为 380V ±10%。 2、制冷剂多或室外机冷凝器过脏。

3、室外风机坏或室外风机调速器坏(在室内机,黒色连接线为 122 和 123)。坏时可以不用, 短接即可。它只是利用系统的压力来控制室外机风机的转速,达到省电目的。 4、热力膨胀阀坏。 故障检测排除:

经用压力表测量制冷系统停机平衡压力为 0.9Mpa (表示系统里氟利昂不多不少)。开机 等空调压缩机启动后,测量接线端子空气开关有市电 380V ±10%电压输入(表示电压正常)。 直观看到室内和室外风机都运行正常。同时看到压力表测量的低压压力表针从 0.9Mpa 慢慢 的降到 0.23 Mpa 后立刻出现“H1 告警”——高压保护。从空调制冷系统原理来分析,这种 现像只有系统堵塞的可能,制冷系统堵塞有两种可能(1、电磁阀坏,不能吸合。2、热力膨 胀阀坏,不能开启或完全开启)。检查该机器时没有电磁阀,可以判断为热力膨胀阀坏,不 能随着铜管温度的变化来开启、达到制冷系统流量所达到的制冷目的。 处理过程:

首先拧开膨胀阀体下端的螺帽,看到一个小的正方体铜旋钮,逆时针方向调是放大系统 冷剂流量,顺时针方向旋转是缩小系统冷剂流量,调节到适当压力制冷正常即可。每次调节 后观察 5-10 分钟再做下次调节。以上分析出来的故障,需逆时针方向旋转,每次调节旋钮 以 1/4 到 1/2 圈为好,调到最大时(已不能在调),空调还是不能够正常制冷,说明热力膨 胀阀完全坏,需更换热力膨胀阀。或应急维修:1、用两把扳手扭开膨胀阀的传动膜的铜帽, 可以看到时里面有一个铁的锥型,锥型顶部下面有一个圆孔(控制制冷系统冷剂的流量), 还有两根小圆铁针(就是利用感温包的传感压力,来用顶开铁锥型上下动作,使之达到一个 开的启大小的作用)。2、人为取来 2-5MM (按实际情况定厚度)的铁垫片来垫高热力膨胀 阀的传动杆,使铁锥型的顶端和圆孔一直保持制冷剂流量达到节流、降温、降压的作用,这 时膨胀阀不在具有自动调节功能,是人为固定截流冷剂的大小,制冷系统的效果只能通过调 整氟利昂的多少来控制。垫好后,重新扭好热力膨胀阀,抽真空加冷剂,开机待压缩机启动 几分钟后,膨胀阀有水珠表明调整成功,试机压力正常,制冷正常。处理完成。

综上所述:调节和应急维修热力膨胀阀应按个人经验,应适具体情况来调整和调节。 案例 16:

依米康 EDA81U 空调整机不工作,操作面板无反应。220V 保险烧坏,上好保险,一开机同 样问题。 问题:

室内风机短路烧坏,引起 220V 保险烧坏 故障分析:

在这我就不单针对室内风机坏问题来分析,把依米康空调从室内到室外机整个电器控制系统 一一分析:

1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、(室内机部分)220V 保险烧坏或变压器烧坏。 3、(室内机部分)控制板故障。

4、(室内机部分)室内风机交流接触或压缩机交流接触器烧坏。 5、(室内机部分)室内风机启动电容坏或室内风机烧坏短路。 6、(室内机部分)压缩机烧坏短路。 7、(室外机部分)室外风机烧坏短路。 故障检测排除:

依米康空调整机不工作,操作面板无反应:1、测量是否有市电或缺相断路,正常。2、

带电分别测量 220V 保险输入端和输出端与零线测量是否有 AC220V ,都有说明保险完好, 输入端有 220V 输出端无 220V 说明保险烧坏。3、测量变压器初级有 220V 交流输入,次级 是否有交流 AC24V 左右输出,有说明变压器完好,无 AC24V 输出说明变压器烧坏。4、变 压器次级输出经过的 AC24V 保险是否完好,测量方法:带电分别测量 24V 保险输入端和输 出端与 4 号线测量是否都有 AC24V ,有说明保险完好,输入端有 24V 而输出端无 24V 说明 保险烧坏。5、AC24V 电压经过保险直接分一组电压给控制面板供电,再由控制面板分出几 组给风机交流接触器,压缩机交流接触器,保护开关等。已有 24V 电压供给控制面板,但 控制面板无反应,无 24V 电压输送给交流接触器线圈,说明控制面板烧坏。6、测量风机交 流接触器线圈(交流接触器上表有 A1、A2)有 AC24V 左右电压又能吸合完好,说明风机 交流接触器完好,无说明交流接触器坏,室内风机不运转。压缩机交流接触器检测,开机 3 到 5 分种后和风机交流接触器一样的测量判断。7、室内风机交流接触器吸合正常,有电输 出供给室内风机,但室内风机不运转,说明室内风机启动电容坏或室内风机本身故障。8、 注明:依米康空调分别有 220V 保险和 24V 保险,只要是 220V 保险烧,说明电压电流过高 或室内风机、室外风机、压缩机等短路。24V 保险烧,说明控制面板烧短路或交流接触器线 圈烧坏短路,应检测利用 24V 控制部分就 OK 。

处理过程:

断电用万用表 200 欧母测量风机各个的线圈绕阻,发现有一组线圈绕阻与风机壳短路。 说明风机内部已短路,更换新的室内风机,开机制冷正常。故障处理完毕!

依米康空调其它故障:

故障现象 1:空调室内风机不运转

判断分析:首先检查控制内风机的交流接触器线圈(A1、A2)是否有 24V 控制交流电, 如果有那就是交流接触器线圈烧坏,使得上下触点不吸合,没有电到那就是控制面板或者相 序保护板烧坏无 24V 电压输出给交流接触器线圈。另一种情况是交流接触器吸合但内风机 仍是不运转,接触器输入与输出端触点氧化导致没有电到内电机,象这类情况可以使用万用 表测量接触器的输入与输出端有没有 220V 交流电。如果接触器也吸合、输出端也有 220V 电压,那就是内电机线圈烧坏了,正常情况下电机的正常阻值在 100Ω以上,同时也不排除 电容损坏的可能性,但依米康内电机电容损坏的机率很少,最常见的是内电机线圈烧坏或者 轴承卡死转不起来。

故障现象 2:压缩机不运转

判断分析:检查控制压缩机的交流接触器是否吸合,如果吸合那就使用万用分别测量输 入与输出端是否有 380V 的交流电压,如果输入与输出都有电压,那就压缩机线圈断路或者 卡缸。

故障现象 3:压缩机工作但不制冷

判断分析:首先排除是否压缩机反相运转,从表面上看反转的声音很大声而且机身抖动 很厉害,产生嗡、嗡声,压缩机的排气管与吸气管没有明显的温差、用压力表测量高压与低 压的压力一样。如果没有反相运转那就是制冷系统已经没有冷剂。

故障现象 4:控制面板出现 H1 高压告警

判断分析:第一、外电机转速变慢引起系统高压保护,面板出现 H1 高压告警;第二、 室外电机的电容被击穿导致电机不运转;第三、膨胀阀堵塞(全堵、半堵、油堵、脏堵)四 种情况都会引起,膨胀阀堵塞只能整个更换或者稍微清洗但会影响到制冷效果。

故障现象 5:控制面板出现 L1 低压告警

判断分析:第一、使用压力表测量低压管(回气管)的压力是否低于 2KG ,如果有那 就是冷剂少或者管路有漏点,需要进行肥皂水检漏;第二、膨胀阀半堵导致流进蒸发器的流 量变少,从而回到压缩机的压力变低。

31

故障现象 6:控制面板无显示

判断分析:第一、控制变压器烧坏(无 220V 交流电输入或无 24V 交流电输出);第二、 保护变压器输入与输出的 2 个保险丝熔断。

故障现象 7:控制压缩机、内风机的 2 个交流接触器不吸合

判断分析:第一、控制面板背后的 52、57 或 58 号线脱落;第二、相序保护板烧坏;第

三、交流接触器线圈烧坏;第四、控制面板烧坏无 24V 控制电压输出。

空调维修实用手册

空调维修实用手册

目录

一.基础理论··································································3 1. 制冷系统基本原理····························································3 2. 空调基本电源控制系统原理····················································3 3. 空调基本结构································································3 3.1. 压缩机····································································3 3.2. 冷凝器····································································4 3.3. 膨胀阀····································································4 3.4. 蒸发器····································································4 3.5. 控制面板···································································5 3.6. 控制变压器·································································5 3.7. 室外、内电机·······························································5 3.8. 三相接触器·································································6 3.9.电机电容·································································· 6

3.10.内风机继电器····························································· 6

4. 空调电机接线图······························································7 二.制冷工具使用操作方法·····················································10 1. 压力表操作方法·····························································10 2. 空调压力的测试和冲加制冷剂流程·············································10 3. 怎样连接管对制冷系统进行抽真空·············································11 4. 管工工具及使用方法·························································12 三.空调的日常维护要求······················································15 四.空调常见故障与分析······················································16 1.电源反相·································································16 2. 空调缺少 R22·······························································16 3. 空调 R22 过多······························································16 4. 空调压缩机故障····························································16 5. 节流阀(热力膨胀阀)故障··················································17 6. 空调室外风机故障··························································17 7. 空调控制面板故障··························································17 8. 空调交流接触器故障························································17 9. 空调变压器故障····························································17 10. 空调感温头故障···························································17 五.基站空调大至常见故障····················································18 1. 空调整机不工······························································18 2. 空调室内机转室外机不转····················································18 3. 空调器不制冷原因··························································18 4. 力博特空调室内机结冰原因··················································18 六.基站空调故障代码总汇····················································18 七.空调维修案例····························································22

1

空调维修实用手册

大金空调····································································22

案例 1:开机运转 25 分钟后整机停机且故障灯一直闪·····························22 格力空调·····································································22

案例 2:开机制冷 8 到 10 分种左右后出现 E1 告警································22 案例 3:格力整机无显示·······················································23

案例 4:室内机工作正常,室外机风扇运转,压缩不运转···························24 海尔三菱空调································································24

案例 5:正常制冷 5 到 10 分种后左右就不能制冷··································24 力博特空调··································································25

案例 6:室内室外机运行正常,但不能制冷,室外机储液灌烫手·····················25 案例 7:整机不工作,操作面板无反应···········································25 案例 8:高温告警, 室内机运行正常,室外机不工作································26 案例 9:空调启动运行后空气开关跳闸的现象·····································27 案例 10:空调控制面板按键失灵················································27 案例 11:空调内机正常运行外机不工作··········································27

案例 12:制冷效果差,内外机都正常,重启后能短时能制冷························28 三洋空调····································································28

案例 13:按“开/关键”开机,整机无反应,灯不亮······························28

案例 14:室内机工作正常,室外机不工作,开机几分钟后出现 E04 告警··············29 依米康空调···································································29 案例 15:开机制冷几分钟后,有 H1 告警·········································29 案例 16:整机不工作,操作面板无反应··········································30 依米康空调其它故障:··························································31 附:空调厂家电话·····························································32

2

空调维修实用手册

一.基础理论

1. 制冷系统基本原理

压缩机排出的高温高压气体经过冷凝器(室外机)通过风机把热量与空气中的介质进行 热交换散热(放热过程)后冷凝变为中温高压的液体制冷剂,然后通过膨胀阀或者毛细管进 行节流降压逐渐变为低压中温的制冷剂液体然后进入蒸发气(室内机)进行蒸发气化逐渐转 化为低温低压的气体,空气中的热量就被蒸发器所吸收,环境的温度就逐渐下降然后空气中 的水分就翻盖在蒸发器的表面上通过底部的接水盘排出室外(如下图)。

2. 空调基本电源控制系统原理:

室内配电箱三相四线引到室外机的接线端或交流接触器的输入端(注:输出端的电压主 要供给压缩机和室外风机使用)。从输入端引 220V 交流电压供室内机使用,经过室内稳压 器进行整流稳压后供给内机电脑板,再分 2 路电源,一路供给室内风机与控制面板、一路输 出低压控制信号,控制外机的低压部分(如三相接触器线圈的工作电压)控制交流接触器的 吸合与断开从而控制压缩机的启动与停止。 3. 空调基本结构 3.1. 压 缩 机

功 能:

1、(循环心脏)提高冷媒压力,以致冷媒可以在高温下冷凝,建立系统运作所需的两个 不同压力

3

2、促使冷媒在系统内流

空调维修实用手册

空调压缩机测量方法是测空调压缩机(380V )的三相阻值是否一样(约 5~9Ω),阻值

为零或差值大的可判断压缩机是坏的。阻值相近的一般情况下是正常的但不排出卡缸和串 气。空调压缩机(220V )的三相阻值是否是 A+B=C。

例: 压缩机三个功能脚的判断,用 RX 1 档测出阻值最大的两端,与这两端所对立的另一端 即为公共 C 端、然后以公共端 C 端为中心,测出其余两个脚的阻值,阻值大的那个脚为启动 S 端、阻值小的为 R 运行端。(C :为公公端、S :启动端、R :运行端) 3.2. 冷凝器

· 冷凝器——

经压缩后的高温高压气体较外面的冷却空气和水温度为高,所以能够将在蒸发器吸取的

蒸发潜热放出来,由冷却空气或水带走,本身却冷凝为液体,功能:把系统中的热放出。 3.3. 膨胀阀

—— 膨胀阀

控制冷媒流到蒸发器的流量,是冷媒由高压到低压差的分界点。当液体通过膨胀阀时,

压力突然降低,一部分液体会突然蒸发,称之闪蒸。闪蒸现象可把其余未蒸发的液体冷 却,变成冷液体。功能:调整冷媒的流量,起到节流、降压、降温的作用。

4

3.4. 蒸发器

空调维修实用手册

蒸发器——

冷媒液体一边流动一边蒸发,不断的吸收外面的热,变成低温气体。同时蒸发器外面的 空气或水便会被冷却。

3.5. 控制面板(参照:力博特、依米康)

作用:控制空调的启动与停止与参数的修改。

3.6. 控制变压器

作用:由交流 220V 电压转换为交流 12V 或者 24V 的低电压供电脑板使用。

空调变压器的测量方法:在带电测量的情况下,用万用表交流挡测量初级有 220V 输入,次

级有交流 24V (依米康、力博特)或交流 12V (其它机子如格力)输出。在断电常温下用万 用表欧姆挡(200Ω挡位)测量变压器的初级线圈阻值为 20Ω,次级线圈阻值为 0.04Ω.初级

5

空调维修实用手册

线圈的阻值比次级要大。 3.7. 室外、内电机

作用:起到加快冷凝器、蒸发器的散热、吸热的作用,强迫与空气进行热交换,加快冷凝、 蒸发的速度。

空调电机的测量方法:(380V )空调外风机三相阻值是否一样,为零的或阻值差距很大的可 判断是坏的,三相阻值相近的一般情况下是正常的,但不排除轴承损坏。(220V )空调内、 外风机三项阻值是否是 A+B=C。 3.8. 三相接触器

作用:交流接触器是利用电磁吸力,使电路接通和断开的一种自动控制电器 主要结构:主触点系统、辅助触点电磁系统、灭弧装置等几部分组成。

三相接触器的测量方法:(1)可以用万用表欧姆挡测量线圈阻值,一般为几百欧到几千 欧。(2)另外按下触点,用万用表测量对应上、下触点看相应的触点是否导通。 3.9.电机电容(符号:C )

作 用:启动作用

定义:凡是被绝缘物分开的两个导体的组合,就叫电容器。 电容的文字符号为:C

电容按极性分为:有极性电容、无极性电容 重要指标: 电容量(uF )、耐压值(380V/220V)

例如:35 uF、220V 表示:电容量为 35 uF、耐压值为 220V 并联电容器的总电容等于各个电容器的电容之和。即:C=C1+C2+C3

6

空调维修实用手册

测量电容方法:

1、可以使用“放电法”进行试验,即金属物体将电容器的两个接点短路,若电容能 正常放电,则说明该电容是好的。

2、用万用表(机械表)的两只表笔接触电容的两极,若表针先指低阻挡,并逐渐退 回高阻挡,表明电容器具用充放电能力,若表针指示在低阻值而不能退回时,表明该电 容已经已极间短路。若表针一开始就指示高阻值或表针不动,则表明已发生极间断路(即 电容器已经被击穿) 3.10.内风机继电器(力博特)

作用:控制室内风机的高低风速

圈正常阻值为 80 欧姆左右。 空调其它保护器:

测量内风机继电器方法:第一,在断电常温下使用万用表的欧姆挡测量 1、3 接线柱线

1、温度保护器,通常用于内风扇电机上,当风机出现堵转,过流、过热时,温度保护器断 开起到保护作用。温度保护器有两种形式,一种是当温度达到某一定值后就会永久性熔断, 这一类称为温度保险丝。另一种是当温度达到某一定值后,就会自动断开电路,当温度下降 到某一允许时,其自动会闭合,这一类称为温度保护开关。 2、 压力开关

压力开关的作用是,监测制冷设备系统中的冷凝高压和蒸发的低压压力值,当压力高于 或低于额定压力值时,压力开关断开,从而切断了控制回路的电源;或者将断开的信号反馈 到主控电脑板,再由电脑控制停机,从而起到保护的作用。

高压开关主要检测高压部分压力,只要低压低于限额度,低压开关就会断开。 好坏判断:高低压开关正常情况下都是导通状态,可用万用表电阻挡测量。 3、 过载保护器

过载保护器分为内置和外置式两种:

(1)内置式过载保护器装于压缩机(comp )里面,直接感受压缩机电机绕组的温度,检测 灵敏度较高。

(2)外置式过载保护器装在压缩机的接线盒内,开口端紧贴在压缩机的外壳上,随时感受 机壳温度,当电源接通时,如果电机不能正常运转,而出现电流过大,发热元件因电流过大 而升温,达到一定温度后自动切断电源回路,起到保护作用。如果压缩机外壳温度升高,同 样起到保护的作用。因此这种过载保护器具有过负荷和过温升双重保护功能。

好坏判断:用万用表电阻挡测量,它的两个接线柱在正常情况下是导通的,若阻值为无穷大, 则说明过载保护器已经损坏。 4.空调电机接线图

机型:力博特外风机接线图(2 版本、3 版本)

7

N

L

空调维修实用手册

L :火线 N :零线

机型:依米康(EDA81U )内风机接线图

Y/G:黄绿(接地) BK :黑色 BL :蓝色

R :红色

Y :黄色

LOW :低风速 M :中风速 HI :高风速 N :零线

8

空调维修实用手册

机型:依米康(EDA81USP )外风机接线图

N :零线

L :火线 BLUE :蓝色

BROWN :棕褐色

OR AND VERDANT:黄绿(接地) SWARTHY :黑色

H:高风速 C:电容 L:火线

M:中风速

L:低风速

S:最低风速

N:零线

9

空调维修实用手册

二.制冷工具使用操作方法

1.压力表操作方法:

一般现在的制冷行业中都是使用复合式双表来测量制冷系统的压力与充加冷剂、抽真空等

用途比较广泛,该表连接如下图。

首先说明几种单位值的换算——

压力单位值换算:

在工程技术中为了计算方便,把大气压力值取为 1kg/㎝² 来使用,在制冷技术中,常使用 兆帕(Mpa )为单位,在我们的压力表表盘上由里向外共有两圈数值刻度值,指出两种压力 数值。一种是英制表示(以 psi 表示)、一种是国际单位制表示(以 1kg/㎝²表示)。 它们之间的关系为:1kg/㎝²=9.8×10Pa=0.1 Mpa ≈ 1Kg ≈14psi 2.空调压力的测试和冲加制冷剂流程。 (1)空调压力的测试:

空调有高低压两个测试压力的工艺口,这两个工艺口和压力表高低压表口相对应接上 {压力表蓝色表管(低压表/真空表)接在空调的大管工艺口上(低压管);压力表红色表管 (高压表)接在空调的小管工艺口上(高压管)},接好后待空调压缩机启动,查看压力表 的压力变化,低压压力在 5~6kg(70~85psi)高压压力在 16~20kg(225~285 psi)是正常 的,压力过低的表明少制冷剂,压力过高的表明制冷剂充得过多。 (2)冲加制冷剂的流程:

空调冲加制冷剂时,将压力表高低压口接到空调高低压工艺口上,压力表中间管口连 接一根加氟管到制冷剂钢瓶上;再将压力表的高低压阀门打开,略扭松开制冷剂钢瓶阀门、 利用钢瓶自身制冷剂压力将压力表管内的空气排出。待空调压缩机启动后把压力表的高压阀

10

门(阀门 1)开关关闭,低压阀门(阀门 2)打开,随后完全打开钢瓶的阀门,制冷剂就会 随着压缩机吸收压力吸入空调制冷系统里;注意观察,待低压压力达到正常值时(正常值: 5~6kg(70~85psi)关掉低压阀门,同时也关闭制冷剂罐开关,观察空调运行 30 分钟压力 变化情况和空调制冷效果,压力都在正常值内,空调制冷正常,冲加制冷剂完成; 最后关机, 迅速扭出压力表高低压口,在用螺帽把空调高低压工艺口扭紧。请看图

3.怎样连接管对制冷系统进行抽真空?

请看下图:

如图所示,表中间连接嘴连接真空泵。

抽真空有三种方法:

(1) 低压单侧抽真空,直接将压力表蓝色表管(低压表/真空表)接在空调的大管工艺口

上(低压管),然后关闭红色表管(高压表)的高压阀门(阀门 1),然后启动真空 泵,随即打开低压阀门(阀门 2)进行抽真空,注意观察低压压力表的指针变化,

(2) 一般抽 30 分钟或指针指在-0.06Mpa 位置,将低压表的阀门关闭,在切断真空泵电

源。 (3) 高低压双侧抽真空 就是在空调高、低压管上的工艺口分别接上管然后进行抽真空。 (4) 复式抽真空

就是对整个制冷系统进行二次以上的抽真空,以获得理想的真空度,

经过一次抽真空后,制冷系统内部保持了一定的真空度。此时关闭高、低压表的阀 门,去掉真空泵接上冷剂钢瓶向系统内充注冷剂(一般充 1~2Kg 就可以了);启动 压缩机运转数分钟,使系统内残存的气体与制冷剂混合,再开启真空泵进行第二次 抽真空,抽空时间至少在 30 分钟以上,这样能使系统内的气体进一步减少,以达到 规定的真空度。这种方法比单侧抽真空效果好,但要损耗一定的冷剂量和时间。

4.管工工具及使用方法: (1)割管刀

割管刀也称为割管器,是专门切断紫铜管、铝管等金属管的工具。

割管刀的使用方法:将铜管放置在滚轮与割轮之间,铜管的侧壁贴紧两个滚轮的中 间位置,割轮的切口与铜管垂直夹紧。然后转动调整转柄,使割刀的切刃切入铜管 管壁随即均匀地将割刀整体环绕铜管旋转。如下图所示:

(2)扩管器

扩管器又称为涨管器。主要用来制作铜管的喇叭口和圆柱形口,扩管器的夹具分成对称 的两半,夹具的一端使用销子连接,另一端用紧固螺母和螺栓紧固。两半对合后形成的孔按 不同的管径制成螺纹状,目的是便于更紧的夹住铜管。

扩管器的使用方法:扩管时首先将铜管扩口端用锉刀锉修平整,然后把铜管放置于相应管径 的夹具孔中,拧紧夹具上的紧固螺母,将铜管牢牢夹死,具体的扩口操作方法如下图:

(3)硬钎焊(氧焊)

硬钎焊也称为氧焊,所需要的焊具为焊枪(焊炬)。所需要的焊接设备有氧气钢瓶、乙 炔气钢瓶(或液化石油气钢瓶)、连接软管及减压表等,使用的焊料为铜磷合金焊条(铜焊 条)。制冷管道的焊接我们一般采用钎焊焊接,意思就是通过可燃气体(液化石油气)和助 燃气体(乙炔)两者在焊炬中混合燃烧时产生的高温火焰,加热被焊材料,熔化焊料使之成 为间隙的充填金属,而使焊件连接,这种焊接方法就称为钎焊。 焊枪操作方法:

首先打开乙炔瓶的阀门开关、在打开氧气瓶的阀门开关,然后在焊枪处慢慢松开乙炔阀 门使得焊嘴有乙炔气体排出(注:记得不要开得过大),接着用打火机点着焊嘴使得乙炔气

体燃烧,再慢慢打开焊枪的氧气阀门(阀门 1 或阀门 2 都可以),调好火焰!在焊接前先对

焊口进行清洁,并且对焊口或管道进行预热,当铜管的颜色呈暗红色时立即将焊条放在焊接 处继续加热,直到焊条充分熔化流向间隙处,并牢固附在管道上时,移去火焰,焊接完毕。 然后先关闭焊枪的氧气阀门,再关闭乙炔阀门,最后关闭氧气、乙炔瓶阀门。要特别注意在 焊接毛细管与干燥过滤器的接口时,预热时间不能过长,焊接时间越短越好,以防止毛细管 加热过度而熔化。氧气过桥是大瓶氧气向小瓶加氧时提供的一种工具。

万用表:

万用表又叫万用电表或万能表,是一种使用极其广泛的具有多种用途和多个量程的直读式仪 表,它又分为指针式万用表与数字万用表。

一般的万用表可以测量直流电流、直流电压、交流电压和电阻等。目前使用比较广泛的是数 字万用表它测量精度高、输入阻抗高、显示直观、读数准确、功能齐全、体积小而且携带方 便等优点。从显示的灵敏度来讲,数字万用表又分有四位数字和五位数字。

数字万用表可测量电量有:直流电压、直流电流、交流电压、交流电流、电阻、电容、二极 管正向压降、三极管直流放大倍数等,有的表还附有交直流大电流(10A )测量各一档,还 具有自动调零和显示极性的功能、超量程和电池低电压显示功能。 钳形电流表:

钳形电流表又称卡表,用于测量交流电流。 钳形电流表使用注意事项:

1、为使读数准确,钳口的两表面应紧密闭合

2、进行电流测量时,被测载流导线的位置应放在钳口中间,以免产生误差。

3、测量前应进行估计一下被测电流的数值范围,选择合适的量程,或先选用较大的量程测 量,然后再视电流的大小选择适当的量程。

4、若要测量较小的电流时,可将导线在钳形铁芯上绕几圈,这时,指针便停留在较大电流 的数值上。把测得的电流值除以绕在钳形铁芯上的导线匝数,即是该导线的电流值。

(图:钳形电流表)

使用万用表欧姆档分别测量压缩机的三个功能脚线圈阻值(CS 、RS 、CR ),应无开路或者 短路的现象,并且不会对地短路。如下图演示:

青岛海尔 KFR-75LW/D(JZ )的停电补偿设定方法:

作用:设定停电补偿功能后,整机运行过程中突然停电,再次恢复供电时,则整机恢复原来

工作状态。

设定方法:在空调内机接通电源正常开机的状态下,5 秒钟内连续按遥控器睡眠键 10 次, 蜂鸣器响 4 声后进入停电补偿状态。

取消方法:5 秒钟内连续按遥控器睡眠键 10 次,蜂鸣器响 2 声后取消停电补偿功能。

三.空调的日常维护要求

机房的空调是否能正常工作,日常维护是非常重要的!并且机房空调是维持机房内一定 温度、保证其它通信设备正常工作的,它对机房起到降温、除湿的作用。所以维护人员应该 做到以下几点:

1、在日常巡检中,注意查看空调内外机是否工作正常!是否制冷,内机显示面板有无显示。 2、显示面板有无告警

3、用万用表测量电源电压三相 380V±10% ,单相 220V±10% 4、空调专线应承受空调额定电流的 1.5 倍。

5、清洗空调内机过滤网、用清洗剂全面清洗外机冷凝器翅片,并且清除挡住冷凝器出风口 物体。

6、用抹布清洁空调室内机表面,清理空调内机过滤网里面风机底部的杂物。 7、检查室内、室外电机是否运转而且固定脚是否牢固有无松动之类。

8、查看室内配电箱中的空调电源线是否老化、发热、接线是否有松动、脱落、地线接地是 否牢固。

9、查看控制面板设定的温度、湿度是否正确(温度 25℃、湿度 60%左右)

10、测量压缩机运行电流及绕组对地绝缘阻值,紧固接线螺丝,检查压缩机的运行噪声和机 身温度是否正常、测量吸、排气压力。

11、注意倾听压缩机的运行声音,有无反转的现象(反转就是反相,故障现象是压缩机嗡嗡 响或者震动很厉害,正常运转下是比较安静的) 12、检查空调有无来电自启功能。

13、当发现有空调故障并且解决不了时,一定要现场反映给项目的空调主管,寻求技术支持, 同时也方便做好故障维修记录。

14、输通机内、给排水管路,更换破损的保温套

15、现场与机房 BSC 核对空调移位、压力告警是否正常,各接线端子是否牢固而且贴有标 签。

16、检查相关控制、电气部分,包括空气开关,接触器等。

17、检查管路各骡纹接口、焊接口有无油迹(一般情况下泄漏处都会有油迹).

四.空调常见故障与分析

1.电源反相

压缩机无排气与吸气压力,没有温差 空调室内和室外机都启动,但不制冷。 解决方法;换相 2. 空调缺少 R22

(1)空调整机运行内机吹出的风不够冷。 (2)空调整机运行外机吹出的风不热。 (3)空调整机频繁启动运行。 (4)出现高温高压报警。 (5)出现低压保护告警。 (6)管路出现结霜现象。 解决方法:冲加制冷剂。 3.空调 R22 过多

(1)空调整机运行不制冷。

(2)会出现高压保护。(外机不工作,内机正常工作) 解决方法:排出多余的制冷剂。 4.空调压缩机故障

(1)空调压缩机烧坏或被电击穿。

(2)空调压缩机卡缸或串气。 (3)空调压缩机运行声音异常。 解决方法:更换压缩机。

空调压缩机测量方法是测空调压缩机(380V )的三相阻值是否一样(约 5~9Ω),阻值 为零或差值大的可判断压缩机是坏的。阻值相近的一般情况下是正常的但不排出卡缸和串 气。空调压缩机(220V )的三相阻值是否是 A+B=C。 5.节流阀(热力膨胀阀)故障 (1)空调运行后不久停机保护。 (2)热力膨胀阀前后管路温差大。 (3)空调制冷效果不好或不制冷。 (4)空调高低压力异常。

解决方法:调节热力膨胀阀开关或更换热力膨胀阀。 6. 空调室外风机故障

(1)空调运行后不久停机保护。 (2)出现高温告警。

(3)空调制冷效果不好或不制冷。

(4)空调外风机的电容损坏也会导致风机的正常运行。 (5)空调外风机运行时的声音异常。 解决方法:更换外风机或外风机电容。

外风机好坏的判断方法是。(380V )空调外风机三相阻值是否一样,为零的或阻值差距很大 的可判断是坏的,三相阻值但不排除相近的一般情况下是正常的,但不排除轴承损坏 。 (220V )空调外风机三项阻值是否是 A+B=C。 7. 空调控制面板故障

(1)空调控制面板无显示或无法操作。 (2)空调停电后无法自起。 (3)空调室内机启动外机不启动。

(4)空调控制面板内有无损坏(保险烧坏,电阻爆裂等) 解决方法:更换空调控制面板。 8. 空调交流接触器故障

(1)空调整机不工作(依米康有这样的现象)。 (2)空调内机工作外机不工作。

(3)空调内机工作外风机工作但压缩机不工作。(交流接触器可能有一或两个触点坏。) 解决方法:更换交流接触器。

交流接触器的判断好坏是,有交流电压 24V 或交流 220V (空调大多是用 24V 的如力博特, 依米康等,用 220V 是格力、松下等国产空调)到交流接触器线圈,如交流接触器不吸合可 判断已坏:如吸合但运行不正常,可测试交流接触器的每组触点是否正常来判断其好坏。 9. 空调变压器故障 空调整机不工作。

解决方法:更换空调内机变压器。

空调变压器的检测方法是用万用表测试空调变压器的初级和次级有无电阻,无电阻可判断已 坏。

10. 空调感温头故障

(1)室内感温头坏,可能出现无法感温不能控温或外机不启动。 (2)室外感温头坏,可能出现外机不启动。

(3)空调不会自停。 解决方法:更换感温头。

感温头好坏的判断是测量其电阻是否正常(5KB 和 15KB )。

五.基站空调大至常见故障

1.空调整机不工作

(1)外部电源故障(如空调电源空开有问题或电源线断路)。 (2)变压器烧坏

(3)室内机电脑板故障(保险管和压敏电阻烧坏) (4)控制面板故障

2.空调室内机转室外机不转

(1)室内机没有通讯信号输送给室外机(室内机电脑板没有信号输出给室外机) (2)室外机交流接触器坏不吸合,压缩机和室外风机得不到电源。 (3)氟多或氟少,引起高压保护开关动作或压缩机过热保护。 (4)室外机冷凝器过脏保护 (5)室外机电脑板故障

(6)室外压缩机烧坏或室外风机烧坏 3.空调器不制冷原因

(1)外部电源故障(如空调电源空开有问题或电源线断路三相错相)。 (2)室内机无压缩机信号输出

(3)室外机保护开关动作(如高、低压保护开关动作,室外机不运转,冷凝器过脏) (4)压缩机接线问题或压缩机故障。 (5)室外机交流接触器坏

(6)室外板故障或室外相序保护器坏

(7)氟多或氟少,引起高压保护开关动作或压缩机过热保护。 4.力博特空调室内机结冰原因

(1)室内风机不运转(启动电容坏或室内风机坏)

(2)室外机交流接触器吸合后沾死,达到设定温度也不能跳开,压缩机常时间运转不停。 (3)2 板本室内温度板坏,3 板本室内线控板坏。

六.基站空调故障代码总汇

空调型号:依米康(EDA81U 、EDA81USP )

1、“H1”——高压保护(冷剂多、室外机过脏、压缩机的电流值>3.5A、室外风机不运转) 2、“L1”——低压保护(冷剂少的原因引起或者系统堵塞) 3、“FIA ”——高温、高压报警(冷剂少) 4、“HT ”——高温报警

5、“FLA ”——风量丢失(过滤网脏、内风机不转或者转速变慢) 6、“HA ”——高温报警(室内温度超出 30℃)

空调型号:力博特(DME027-PWC2、DME027-PWC3)

1、 HIGH TEMPERATURE ALARM——高温报警(室内回流空气温度升高至高温报警设

定值;需重新设定高温报警值)

2、 LOW TEMPERATURE ALARM——低温报警(室内回流空气温度降低至低温报警设定

值;需重新设定低温报警值)

3、 LOSS OF AIR FLOW——气流量低(把风速调为高速就可以解决)

4、 室内风机不运转——(1)室内风机继电器线圈烧坏,更换继电器或者临时短接。(2)

内风机的线圈烧坏,正常阻值为 100 欧姆以上

5、 室外风机线圈烧坏导致空调不制冷,正常正常阻值为 100 欧姆以上 6、 室外机的保险丝烧坏

7、 空调室外机不工作!无 24V 控制电压输出给外机!内机接口板烧坏更换内机接口板 8、 空调反相!故障现象:压缩机无排气与吸气压力没有温差,压缩机很响有嗡嗡的声音!

解决方法就是换相。 9、 控制变压器线圈烧坏

海尔(LF73WDT 、KFR-71LW/(JZ ):

1、 到目前只发现一种故障,空调显示“E40”是市电电压不稳定造成(缺相或者电压过高),

重新启动空调就可以恢复制冷。

2、 不能自起(自起功能失去作用)或者其它故障。

3、 空调反相(现象:控制面板可以显示而且是在制冷(﹡)的模式下,外风机也运转;但

空调出风口不冷)换相。 格力空调故障代码:

三菱海尔重工故障代码

三菱电机空调 PSH 系列空调故障代码灯:

室外机 LED 故障灯: LED1 相序接反 LED2 缺相

LED3 室外传感器异常 LED4 63H2 功能(传感器) LED5 51C 功能(压力开关) LED6 26C 功能(压力开关) LED7 过热保护

LED8 控制输入电路异常

松下空调故障代码:

大连三洋空调机常见的故障代码及处理方法

7 8 9 10 11 12 13 4 5

P02

无冷剂引起压缩机热保护

雷击或高电压而引起外机电路板或变压 器烧坏(或室内外机相连的控制线路故 障)

内机检测到遥控器或机组控制的异常信 号

串行信号的发送故障 串行信号的接收故障

室内机组的型号与室外机组不匹配 室内机组的容量码没有设定 室内机组型号设定错误(容量) 不能探测室内机侧热交换器温度 不能探测室内机侧热交换器温度

检查是否有泄漏点, 处理后抽空, 加制冷剂 更换室外机电路板或变压器(检查控制线 路)

E04

6 E03 E02 E01 L02 L09 L13 F01 F02

控制线路被干扰, 检查干扰源, 断电重起. 检查控制线路部份 检查控制线路部份

重设室外机型号(地址码开关) 设定室内机容量码 重设室内机型号(容量) 检查室内机感温包(E1=TH2) 检查室内机感温包(E2=TH3)

一般是室外机散热器赃堵或散热不好, 检 查室外机排气感温包(PC 压缩=THOA) 检查室外机感温包(C1=THOE) 检查室外机感温包(C2=THOC) 检查压缩机工况

检查压缩机转子工况(一般情况是卡住) 检查电源相序各接触点是否良好 检查制冷剂是否不足

14

F04

不能探测排气温度

15 16 17 18 19 20

F06 F07 H01 H02 H03 H06

不能探测室外热交换器的液体温度 不能探测室外热交换器的气体温度 PC 压缩机用电动机过载 PC 压缩机用电动机锁定 压缩机的电流检查电路异常 低压开关

七.空调维修案例 大金空调

案例 1: 故障现象:

开机制冷,运转 25 分钟后,整机停机,故障灯一直闪。 问题:

管温热敏电阻变值 故障分析:

1、连接线接触不良 2、市电电压不稳定 3、管温热敏电阻变值 故障检测排除:

开机运转,制冷也正常。但过了 20 分钟以后,未达到设定温度就停机,故障灯一直闪。 检查市电和连接线均无发现有问题,用 202K Ω挡测量室内管温热敏电阻发现阻值才有 2K Ω (常温下正常值应在 5—10K Ω),开机一段时间后,导致控制板误动作。 处理过程:

更换上好的室内管温热敏电阻,试机正常。

格力空调

案例 2:

故障现象:

格力 KF-72LW(72332)-R-N5 开机制冷 8 到 10 分种左右后出现 E1 告警, E1 告警是格 力空调其中的故障代码(压缩机电流过大保护,压缩机过热保护,室外机排气温度过高保护, 室外机相序电流保护电路板坏)。重新断电开机后故障现象一样。 问题:

室外机积太多尘土,太脏倒至空调过热保护 故障分析:

在这就把格力 KF-72LW(72332)-R-N5 机型出现 E1 告警所有问题全部列出: 1、氟利昂多引起高压保护器动作(断开)。

2、该机使用的时间过长,制冷系统内部有泄漏处理完后常加冷剂或更换过压缩机不注意, 脏物入进制冷系统引起毛细管堵塞不能达到节流、降温、降压作用。倒至空调器高压压力过 高、低压压力过低,压力保护器动作(断开)。

3、室外风机坏(注:风机启动电容坏,风机也是不动转),不转,倒至保护器动作(断开)。 4、室外机相序电流保护电路板坏

5、室外机凝器积太多尘土、太脏倒至空调过热保护 故障检测排除:

经过检测,空调器制冷时用压力表测量低压压力过高为 0.75 Mpa(0.5~0.6 Mpa),停机后 平衡压力为 0.9Mpa (表示系统里氟利昂不多不少)。该机使用的时间只有一年,并且没有更 换过压缩机,空调器制冷时用压力表测量低压压力为 0.75 Mpa 不是负压状态,可以排除毛 细管堵塞的可能。空调器制冷时直观室内风机和室外风机都正常运行,可以排除风机坏的可 能。如果是室外机相序电流保护电路板坏,空调器室内机运行 3 到 5 分钟后,室内机电脑 板输送信号给室外机相序电流保护电路板时就马上出现 E1 告警,空调器是不能够制冷的。 由此可见,只有室外机凝器积太多尘土、太脏倒至空调过热保护出现 E1 告警。 处理过程:

清洗干净空调室外机冷凝器,试机正常,故障处理完毕!

注:1、发现 E1 告警,又不是室外机过脏过热保护时,最大的可能原因是室外机相序电流 保护电路板坏,在没有配件更换的情况下,我们可以临时跳开不用。方法:打开室内机底下 面盖,在打开室内机风机顶上的铁皮盖就可以看到室内机电脑板上有一根黄色电源线(标有 OVC 字母,这根线就是保护线),找一根电源线从室内机零线接好引到这根黄色线上(在电 脑板上不能取肖它,照常接好,只是多引一根零线和它串连),连接好后空调就能够制冷正 常,如果还是不能够制冷说明室外机保护继电器坏。

注:2、到了基站我们发现格力室内和室外机都运行正常,又是在制冷模试状态下,空调不 能制冷时,原因是空调器三相错相,更换好相序即可制冷。 案例 3: 故障现象:

格力 KF-72LW(72332)-R-N5 整机无显示 问题:

室内机变压器烧坏 故障分析:

基站格力空调室内机是由交流市电 220 伏供给,220 伏经过压敏电阻和保险丝在到变压器初 级变压后次级为 AC12~14V 左右输出供给室内电脑板使用。由此我们可以分析为: 1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、变压器烧坏或室内机电脑板上的保险、压敏电阻(ZNR )烧坏。 3、室内机电脑板上的稳压元件 7812 或 7805 损坏。

4、操作板故障(如接线松动或按键损坏) 故障检测排除:

按“开/关键”开机,整机无反应。打开室内机接线盒,检查接线端子已有市电 220±10% 电压输入。再检查室内机电脑板上的保险丝和压敏电阻均良好,再测量检查变压器的初级有 AC220V ,次级没有有 AC12~14V 左右输出,正明变压器已烧坏。 处理过程:

更换上好的变压器,试机正常。 案例 4: 故障现象:

格力 KF-72LW(72332)-R-N5 室内机工作正常,室外机风扇运转,压缩不运转。 问题:

室外机三相保护器坏 故障分析:

1、室内机工作正常,室外机风扇也运转(说明室内机没有故障,已有信号输送到室外机) 2、室外机故障:一、压缩机坏。二、市区电缺相。三、压缩机交流接触器坏。四、三相保 护器坏。 故障检测排除:

室内机工作正常,室外机风扇也运转(说明室内机没有故障),打开室外机则盖发现压缩机 不工作。测量市电已有 380V 电压到室外机,在测量三相保护器上的接线触点发现(A 点与 零线测量有 220V ,但是 C 点与零线测量没有 220V ,正明三相保护器已坏) 处理过程:

更换上好的三相保护器,试机正常。

海尔三菱空调

案例 5: 故障现象:

海尔三菱重工 3 匹机,室外机空调连接铜管被盗,重新焊接好连接管,抽真空加氟利昂,开 机前 3 分钟后,室内机和室外机运行正常,每次重新开机都只能正常制冷 5 到 10 分种后左 右就不能制冷。 问题:

空调制冷系统冰堵 故障分析:

1、 查三相供电电压是否正常,三相接线端子是否都接稳接捞。因为空调压缩机启动时电流

比较大,如果电压不稳定,接线接触不良,电流会不断慢慢增大,倒至电流保护或压缩 机热保护。

2、 室内和室外机通信是否正常。海尔三菱重工重新开机后 3 到 5 分钟,从室内机电脑板输

送信号给室外机,室外机才能够得到信号正常运行。

3、 空调分为两大系统(控制电器系统和制冷系统)。空调器的高、低压保护器是否动作,

充加氟利昂时是否加多或加少。 故障检测排除:

1、 经测量三相供电电压都很正常(380V±10%),三相接线端子接线也很捞固。由此可以排

除电压不稳定问题。

2、 开机 3 分钟后,室内室外机运行正常,能够正常制冷 5 到 10 分种才不能制冷。由此可

见,可以排除内外机通信信号异常的可能。

3、 制冷几分钟后,空调压力保护器动作(断开)。在空调还能够正常运行时,用压力表 量空调压力:高压压力特别高,低压压力在从正常制冷时的 0.5Mpa ,运行几分钟后缓慢变 小,最后到负压,空调保护器动作停机,停机 15 到 20 分钟后平衡压力逐步慢慢回升至 0.9Mpa 左右(表示氟利昂充加不多不少)。经过逐步分析到这,就可以找到故障的原因:由于该机 室外铜管被盗,压缩机吸入大量潮湿空气或大量水份,致使制冷系统里积存了大量的水分, 当焊接好连接铜管抽真空充注好氟利昂后,空调机制冷工作时,水分和氟利昂混合在一起, 经过压缩机高压排气到毛细管:节流、降温、降压后,水份结成冰,堵塞毛细管,使空调器 制冷系统不能够组成制冷巡环的过程。本机工作情况明显是冰堵。 处理过程:

放掉制冷系统中的氟利昂,在高压管截流毛细管前端加焊一个能够扭开放出硅胶的干燥 硅胶过滤器,重新抽真空加冷剂。其后第一次开机运行 15 分钟左右收氟关机,打开干燥硅 胶过滤器,把里面由原来的蓝色硅胶变成变白色硅胶放出来,重新在加入硅胶,扭好,排空 气在运行,第二次运行 30 分种左右,在放出变为白色的硅胶。以此操作 3 到 4 次左右,直 到放进去的硅胶在也不会变面白色(表明制冷系统里面已不在有水份)。收好氟后,即可将 过滤器拆除,重新焊接好铜管,排室内机管道里的空气,试机 30 分钟制冷正常。故障处理 完毕!

力博特空调

案例 6: 故障现象:

力博特空调室内室外机运行正常,但不能制冷,停机重新开机后有时又能制冷一下,到现场 用手摸室外机储液灌感觉很烫手。 问题:

室外机平衡阀坏,有时串气引起制冷系统流向错,制冷系统不经过室内机蒸发器循环,倒至 不能够达到制冷系统 4 大件循环的目的。 故障分析:

室内室外机启动正常,但不制冷,由此可以考虑到空调器电器部分没有问题,只有检测制冷 系统部分: 1、氟利昂多或少。

2、热力膨胀阀坏,不能达到节流、降温、降压作用。

3、电磁阀坏或室外机冷凝器灰尘积多过脏, 引起室外机保护继电器动作(断开)。 4、室外机平衡阀坏, 引起制冷系统流向错 故障检测排除:

经过检测,用压力表测量制冷系统停机平衡压力为 0.9Mpa (表示系统里氟利昂不多不 少),检查室外机保护继电器是否动作(断开)都为正常(表示电磁阀正常,室外机冷凝器 没有因灰尘积多过脏),当时以为是电压相序错,调相序后一样不能够制冷, 最后用手摸储液 灌感觉很烫手,正常时储液器不是烫手反而有点冰凉,由此可以断定是室外机平衡阀串气, 冷剂经过压缩机吸收压缩后排出的高温高压气体冷剂流向冷凝后直接循环回储液灌到压缩 机,冷剂没有循环到室内机蒸发器和热力膨胀,所以达不到空调 4 大件制冷系统循环的目的。 处理过程:

将系统内冷剂全部放空,焊出平衡阀不用,不会影响制冷效果(此阀的主要作用是保证 流经冷凝器内的冷媒量保持稳定,其实现在的定频压缩机在额定工况下输出冷媒量是比较稳 定,所以此阀可以不用),重新连接焊好制冷系统回路,抽空加氟利昂,开机制冷正常。故 障处理完毕!

案例 7: 故障现象:

力博特空调整机不工作,操作面板无反应。 问题: 变压器烧坏 故障分析:

在这我就不针对变压器单一问题来分析,把力博特空调(2 板本和 3 板本)从室内到室外机 整个电器控制系统一一分析:

1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、(室内机部分)变压器烧坏。

3、(室内机部分)变压器次级输出端保护开关动作(断开) 4、(室内机部分)电源接口板烧坏 5、(室内机部分)风机继电器烧坏 6、(室外机部分)保护继电器动作 7、(室外机部分)交流接触烧坏 故障检测排除:

力博特空调通常接线:380 伏电压从空气开关直接接到室外机交流接触器输放端(注: 也有少部分力博特空调是 220V 的,从空开接 220V 电压到力博特空调室外机交流接触器输 入端的,该机为 220V 压缩机),室内机另从空开供给 220V 电压。整机不工作,操作面板无 反应:1、测量是否有市电或缺相断路,正常。2、测量变压器初级有 220V 交流输入,次级 是否有交流 AC24V 左右输出,有表示变压器完好,无 AC24V 输出表示变压器烧坏。3、变 压器次级输出端保护开关是否动作,如动作,重新按回去即可(它的作用是:电压电流过大 时,动作断开保护后面的电路断开)。4、变压器次级有 24V 左右电压输出,正级接入电源 接口板,另一根(白色)接机壳。测量风机继电器线圈(面对机子,风机继电器最低部那两 根)1 口和 3 口有 AC24V 左右电压和测量室内机连到室外机的接线端子 1、2、3 号线(棕、 红、橙)端子,1 号和 2 号线或 1 号和 3 号线有 24V 左右交流电输出(表示电源接口板已有 信号输出,电源接口板无故障)。5、测量风机继电器线圈 1 口和 3 口有 AC24V 左右电压, 再测量面对风机继电器最左上角的端子和 220V 零线是否有 220V 电压,有表示这个继电器 完好,无表示继电器坏室内风机不运转。6、室外机保护继电器到目前还没有发现坏过,它 的作用是:制冷系统压力过高保护,电压电流过大保护。正常制冷时,它是由室内机接线端 子 1、2、号线(棕、红)输入 24V 电压,再由这个保护继电器来控制室外机的交流接触器 线圈。有时发现空调器能制冷几分钟后,室外机不运转,就是这个保护继电器动作,这时测 量不是 1 号和 2 号线(棕、红)有 24V 电压,反是 1 号和 3 号线(棕、3 号橙色是保护线) 有 24V 电压。1 号和 3 号线有 24V 电压,表示制冷系统压力过高保护,可能的原因有:室 外风机不运转,氟利昂多,室外机冷凝器过脏,电磁阀不吸合。7、室外交流接触器是控制 压缩机和室外风机供电启动的重要元器件,交流接触烧坏,室外机整机不工作。测量方法: 只要交流接触器线圈有 AC24V 电压,交流接触又能吸合正常(表示交流接触器完好 ),测 量线圈有 AC24V 电压,但交流接触又不能吸合(表示交流接触器线圈已烧坏,已不能在使 用)。 处理过程:

测量有交流市电 220V 电压到空调室内机。再测量变压器初级有 220V 交流输入,测量变压 器次级无交流 24V 输出(表示变压器烧坏),更换新的变压器,开机制冷正常。故障处理完 毕! 案例 8:

力博特空调高温告警, 室内机运行正常. 室外机不能工作 问题:

室外机三相交流接触器坏,导致室外机不能工作 故障分析:

力博特空调高温告警, 室内机运行正常,室内机运行正常,室外机不能工作。有制冷式 COOL. 但不能制冷。 可能原因有:

1:内机接口板坏,没有 24V 电压送给外机保护继电器

2:保护继电器坏,没有 24V 电压送给室外机三相交流接触器坏 3:室外机三相交流接触器坏,室外风扇电机和压缩机没得到市区电。 故障检测排除:

用万用表来测量,室外机三相交流接触器线圈已获有交流 24V 电压(表明内机接口板和外 机保护继电器是完好的),交流接触器线圈已获有交流 24V 电压但外机三相交流接触器伋不 吸合。断电用电阻档量三相交流接触器线圈无穷大。这时证明三相交流接触器线圈已烧坏, 更换三相交流接触器,试机正常。 处理过程:

更换三相交流接触器,试机正常。 案例 9: 故障现象:

力博特空调启动运行后空气开关跳闸的现象。 故障分析:

空调电源部分有对地或配件短路。 处理办法:

首先关电,再用万用表(欧姆挡)开始从空调电源线路开始检查或选择性的排查。

其次检查看线路有没有短路或对地。空调线路短路主要是注意线和线之间有没有短路或空调 配件烧坏造成内部短路,线路短路主要是电路板和一些保险装置损坏;空调线路对地主要检 查火线是否有直接对地的或配件烧坏后导致对地的,线路对地主要是火线和压缩机、内外风 机绕阻损坏对地。

检查出故障点后,整改线路或更换损坏配件,最后开机试机查看是否恢复。 案例 10: 故障现象:

力博特空调控制面板按键失灵现象。 可能有的故障:

空调控制面板坏或低压电压异常。 处理办法:

首先检测电源部分的低压部分供电是否正常(主要是空调内机变压器的好坏),变压器使用 24V 。检测办法是用万用表(200 殴)检测,线圈的阻值(初级是 13 左右殴、次级 6 殴这样 左右),超出范围或无限的可判断已坏。也可以带电测量,用万用表电压档检测查看有没有 24V 输出,有 24V 输出表示正常,如超出范围表示已损坏。

其次空调低压部分正常,就可能是电路板坏,主要是检电路板的保险部分是否完好和输出给 控制面板的直流 5V (N5 和 T 口电压)否正常来判断。

检查出故障点后,更换损坏的控制面板配件,最后开机试机查看是否恢复。 案例 11:

力博特空调内机正常运行外机不工作。 可能有的故障: 1、电路板故障。 2、元件故障。 3、系统故障。 处理办法: 电路故障。

外机到电的启动过程。

(市电 380V 外机同时引 220V 到内机,内机的 220V 通过变压器后输出 24V 交流低压给 电路板检测,检测后的 24V 提供给外机的交流接触器工作,交流接触器工作后外机启动运 行) 根据启动过程一路排查元件和线路的好坏排查。

首先检测市电是否正常(线电压 380V 左右,相电压 220V 左右),在市电正常情况下停 电用万用表欧姆档检测空调电路,先检测电源部分的低压部分供电是否正常(主要是空调内 机变压器的好坏),变压器使用 24V 。检测办法是用万用表(200 殴)检测,线圈的阻值(初 级是 13 左右殴、次级 6 殴这样左右),超出范围或无限的可判断已坏。也可以带电测量,用 万用表电压档检测查看有没有 24V 输出,有 24V 输出表示正常,如超出范围表示已损坏。 变压器输出 24V 通过室内电路板检测后,传到外机交流接触器,如无输出就可能是电路板 坏,电路板检测主要是检电路板的保险部分是否完好和输出给控制面板的直流 5V (N5 和 T 口电压)否正常来判断。有 24V 到外机后还有检测交流接触器好坏(交流接触器主要检查 线圈电阻是否在 6 殴左右和触电的好坏)才检测完线路和元件。 系统故障。

(系统压力过低或过高,低压保护开关和高压保护开关动作保护空调,外机不启动或启 动平凡)

检测办法首先用压力表检测系统静压压力,正常的静压在九到十公斤左右,如果低于表 示压力过低,需充加制冷剂,如过高排出制冷剂。 案例 12: 故障现象:

力博特制冷效果差,内外机都正常,重启后能短时能制冷。 可能存在问题: 1、 平衡阀故障。 2、 膨胀阀问题。 处理办法:

1、平衡阀主要平衡压力的,损坏后制冷剂不通过蒸发器循环,空调不能制冷,需更换平衡 阀。

2、膨胀阀在系统中主要是节流降压作用,膨胀阀坏系统可能出现堵塞,出现系统压力参数 改变,制冷效果差或不制冷。出现的现象有膨胀阀前后的温差很大或系统高低压压力高压偏 高低压偏低。修复需要更换膨胀阀。

三洋空调

案例 13: 故障现象:

三洋 SPW-V253DHL5 机型,按“开/关键”开机,整机无反应,灯不亮。 故障分析:

1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、变压器烧坏或室内机电脑板上的保险、压敏电阻(ZNR )烧坏。 3、室内机电脑板上的稳压元件 7812 或 7805 损坏。 4、操作板故障(如接线松动或按键损坏) 故障检测排除:

按“开/关键”开机,整机无反应。检查接线端子空气开关是有市电 380V ±10%电压输入。 有,再检查室内机电脑板,保险丝和压敏电阻均良好,再测量检查变压器的初级有(AC 代 表交流电压)AC220V ,次级有 AC12~14V 左右输出,正明变压器正常。再检查电脑板的 稳压元件 7812 或 7805,7812 没有+12V 输出,说明电脑板故障。 处理过程:

申请室内电脑板更换,试机正常,故障处理完毕!

注:1、如果直观看到室内机电脑板保险、压敏电阻(ZNR )烧坏,我们在断开电源空开下 可以临时小心撇断压敏电阻(ZNR ),更换上好的保险,开机,试机正常运行。 案例 14: 故障现象:

三洋 SPW-V253DHL5 机型,室内机工作正常,室外机不工作,开机几分钟后出现 E04 告警。 问题:

室外机电脑板上的保险和压敏电阻(ZNR )烧坏。 故障分析:

1、室内机没有信号输送到室外机或室内室外机连接线故障。

2、室外变压器烧坏或室外机电脑板故障或室外机电脑板上的保险和压敏电阻(ZNR )烧坏。 故障检测排除:

打开检查室内机电脑板,没有发现有烧坏的元器件。开机几分种后,测量室内机接线端子的 信号线输出正常(说明室内机没有故障)。打开室外机的则盖发现室外机电脑板上的保险和 压敏电阻(ZNR )都烧黒(说明保险和压敏电阻已烧坏需要更换)。同时我们要测量一下室 外机变压器是否完好,因为有时保险和压敏电阻烧坏时,变压器同时也会烧坏。测量变压器 方法:断电 200Ω挡测量初级通常会比次级大 10 倍以上(说明是好的)。 处理过程:

断开电源空开,临时小心撇断压敏电阻(ZNR )不要,更换上好的保险,开机,试机正常运 行。工具包带有压敏电阻,最好也要更换上好的压敏电阻,这样能够更好的保护室外机电脑 板。或更换新的室外机电脑板。

依米康空调

案例 15: 故障现象:

依米康空调 EDA81U 开机制冷几分钟后,有 H1 告警。 问题:热力鼓胀阀坏。

热力膨胀阀是制冷系统中重要的截流设备,它工作的正常与否直接关系到制冷系统制冷的效 果。工作原理:通过感温包感受蒸发器出口处铜管温度的变化,导致感温系统内产生不同的 压力,使传动膜片(波纹管)形成上下位移,并将此传递给传动杆从而推动阀针上下移动, 使阀门关小或开大,起到节流、降温、降压作用。膨胀阀通常是不能完全关闭的。膨胀阀阀 芯的行程一般不超过 6MM ,但也与膨胀阀的规格大小有关。 故障分析:

“H1”——高压保护(冷剂多、室外机过脏、压缩机的电流值>3.5A、室外风机不运转)

1、外部电路电压不稳定(高或低),电流值过大,正常测量电压为 380V ±10%。 2、制冷剂多或室外机冷凝器过脏。

3、室外风机坏或室外风机调速器坏(在室内机,黒色连接线为 122 和 123)。坏时可以不用, 短接即可。它只是利用系统的压力来控制室外机风机的转速,达到省电目的。 4、热力膨胀阀坏。 故障检测排除:

经用压力表测量制冷系统停机平衡压力为 0.9Mpa (表示系统里氟利昂不多不少)。开机 等空调压缩机启动后,测量接线端子空气开关有市电 380V ±10%电压输入(表示电压正常)。 直观看到室内和室外风机都运行正常。同时看到压力表测量的低压压力表针从 0.9Mpa 慢慢 的降到 0.23 Mpa 后立刻出现“H1 告警”——高压保护。从空调制冷系统原理来分析,这种 现像只有系统堵塞的可能,制冷系统堵塞有两种可能(1、电磁阀坏,不能吸合。2、热力膨 胀阀坏,不能开启或完全开启)。检查该机器时没有电磁阀,可以判断为热力膨胀阀坏,不 能随着铜管温度的变化来开启、达到制冷系统流量所达到的制冷目的。 处理过程:

首先拧开膨胀阀体下端的螺帽,看到一个小的正方体铜旋钮,逆时针方向调是放大系统 冷剂流量,顺时针方向旋转是缩小系统冷剂流量,调节到适当压力制冷正常即可。每次调节 后观察 5-10 分钟再做下次调节。以上分析出来的故障,需逆时针方向旋转,每次调节旋钮 以 1/4 到 1/2 圈为好,调到最大时(已不能在调),空调还是不能够正常制冷,说明热力膨 胀阀完全坏,需更换热力膨胀阀。或应急维修:1、用两把扳手扭开膨胀阀的传动膜的铜帽, 可以看到时里面有一个铁的锥型,锥型顶部下面有一个圆孔(控制制冷系统冷剂的流量), 还有两根小圆铁针(就是利用感温包的传感压力,来用顶开铁锥型上下动作,使之达到一个 开的启大小的作用)。2、人为取来 2-5MM (按实际情况定厚度)的铁垫片来垫高热力膨胀 阀的传动杆,使铁锥型的顶端和圆孔一直保持制冷剂流量达到节流、降温、降压的作用,这 时膨胀阀不在具有自动调节功能,是人为固定截流冷剂的大小,制冷系统的效果只能通过调 整氟利昂的多少来控制。垫好后,重新扭好热力膨胀阀,抽真空加冷剂,开机待压缩机启动 几分钟后,膨胀阀有水珠表明调整成功,试机压力正常,制冷正常。处理完成。

综上所述:调节和应急维修热力膨胀阀应按个人经验,应适具体情况来调整和调节。 案例 16:

依米康 EDA81U 空调整机不工作,操作面板无反应。220V 保险烧坏,上好保险,一开机同 样问题。 问题:

室内风机短路烧坏,引起 220V 保险烧坏 故障分析:

在这我就不单针对室内风机坏问题来分析,把依米康空调从室内到室外机整个电器控制系统 一一分析:

1、外部电路出现问题(如空调电源空开有问题或电源线断路)。 2、(室内机部分)220V 保险烧坏或变压器烧坏。 3、(室内机部分)控制板故障。

4、(室内机部分)室内风机交流接触或压缩机交流接触器烧坏。 5、(室内机部分)室内风机启动电容坏或室内风机烧坏短路。 6、(室内机部分)压缩机烧坏短路。 7、(室外机部分)室外风机烧坏短路。 故障检测排除:

依米康空调整机不工作,操作面板无反应:1、测量是否有市电或缺相断路,正常。2、

带电分别测量 220V 保险输入端和输出端与零线测量是否有 AC220V ,都有说明保险完好, 输入端有 220V 输出端无 220V 说明保险烧坏。3、测量变压器初级有 220V 交流输入,次级 是否有交流 AC24V 左右输出,有说明变压器完好,无 AC24V 输出说明变压器烧坏。4、变 压器次级输出经过的 AC24V 保险是否完好,测量方法:带电分别测量 24V 保险输入端和输 出端与 4 号线测量是否都有 AC24V ,有说明保险完好,输入端有 24V 而输出端无 24V 说明 保险烧坏。5、AC24V 电压经过保险直接分一组电压给控制面板供电,再由控制面板分出几 组给风机交流接触器,压缩机交流接触器,保护开关等。已有 24V 电压供给控制面板,但 控制面板无反应,无 24V 电压输送给交流接触器线圈,说明控制面板烧坏。6、测量风机交 流接触器线圈(交流接触器上表有 A1、A2)有 AC24V 左右电压又能吸合完好,说明风机 交流接触器完好,无说明交流接触器坏,室内风机不运转。压缩机交流接触器检测,开机 3 到 5 分种后和风机交流接触器一样的测量判断。7、室内风机交流接触器吸合正常,有电输 出供给室内风机,但室内风机不运转,说明室内风机启动电容坏或室内风机本身故障。8、 注明:依米康空调分别有 220V 保险和 24V 保险,只要是 220V 保险烧,说明电压电流过高 或室内风机、室外风机、压缩机等短路。24V 保险烧,说明控制面板烧短路或交流接触器线 圈烧坏短路,应检测利用 24V 控制部分就 OK 。

处理过程:

断电用万用表 200 欧母测量风机各个的线圈绕阻,发现有一组线圈绕阻与风机壳短路。 说明风机内部已短路,更换新的室内风机,开机制冷正常。故障处理完毕!

依米康空调其它故障:

故障现象 1:空调室内风机不运转

判断分析:首先检查控制内风机的交流接触器线圈(A1、A2)是否有 24V 控制交流电, 如果有那就是交流接触器线圈烧坏,使得上下触点不吸合,没有电到那就是控制面板或者相 序保护板烧坏无 24V 电压输出给交流接触器线圈。另一种情况是交流接触器吸合但内风机 仍是不运转,接触器输入与输出端触点氧化导致没有电到内电机,象这类情况可以使用万用 表测量接触器的输入与输出端有没有 220V 交流电。如果接触器也吸合、输出端也有 220V 电压,那就是内电机线圈烧坏了,正常情况下电机的正常阻值在 100Ω以上,同时也不排除 电容损坏的可能性,但依米康内电机电容损坏的机率很少,最常见的是内电机线圈烧坏或者 轴承卡死转不起来。

故障现象 2:压缩机不运转

判断分析:检查控制压缩机的交流接触器是否吸合,如果吸合那就使用万用分别测量输 入与输出端是否有 380V 的交流电压,如果输入与输出都有电压,那就压缩机线圈断路或者 卡缸。

故障现象 3:压缩机工作但不制冷

判断分析:首先排除是否压缩机反相运转,从表面上看反转的声音很大声而且机身抖动 很厉害,产生嗡、嗡声,压缩机的排气管与吸气管没有明显的温差、用压力表测量高压与低 压的压力一样。如果没有反相运转那就是制冷系统已经没有冷剂。

故障现象 4:控制面板出现 H1 高压告警

判断分析:第一、外电机转速变慢引起系统高压保护,面板出现 H1 高压告警;第二、 室外电机的电容被击穿导致电机不运转;第三、膨胀阀堵塞(全堵、半堵、油堵、脏堵)四 种情况都会引起,膨胀阀堵塞只能整个更换或者稍微清洗但会影响到制冷效果。

故障现象 5:控制面板出现 L1 低压告警

判断分析:第一、使用压力表测量低压管(回气管)的压力是否低于 2KG ,如果有那 就是冷剂少或者管路有漏点,需要进行肥皂水检漏;第二、膨胀阀半堵导致流进蒸发器的流 量变少,从而回到压缩机的压力变低。

31

故障现象 6:控制面板无显示

判断分析:第一、控制变压器烧坏(无 220V 交流电输入或无 24V 交流电输出);第二、 保护变压器输入与输出的 2 个保险丝熔断。

故障现象 7:控制压缩机、内风机的 2 个交流接触器不吸合

判断分析:第一、控制面板背后的 52、57 或 58 号线脱落;第二、相序保护板烧坏;第

三、交流接触器线圈烧坏;第四、控制面板烧坏无 24V 控制电压输出。


相关文章

  • 2012通信电源维护标准规范
  • 中国移动陕西公司 通信电源维护标准规范手册(2011年修订) 第一章 总 则 第一条 为进一步加强全省通信电源设备维护管理,有效提升专业维护工作水平,实现标准化.规范化.样本化维护目标,确保日常维护工作有序开展,特制定本手册. 第二条 本手 ...查看


  • 基站维护工作介绍
  • 基站维护工作介绍 很多人很羡慕搞通信工程和通信设备维修的.这些维修工作中.基站维修是世界上最危险的工作不为过也. 维护的是移动GSM发射塔和塔下机房上千万电子设备,听起来很有魅力. 其实里面电子设备很少坏的.基本都是跑来跑去.换换电池.换换 ...查看


  • 巡检工作的基本要求
  • 培训记录 第一章 巡检工作的基本要求 第一. 巡检工作安排 当天的工作安排主要依据周计划安排,同时须结合当天的天气情况:维护站主管要依据发电情况.故障处理情况.基站重要程度.基站地理位置等合理统筹安排巡检线路,将维护人员合理的分配到相应的工 ...查看


  • 移动基站电源监控与电源维护实例
  • 移动基站电源监控与电源维护实例 ■<广西机电职业技术学院 秦培林,张小衡,黄 麟 摘要:移动基站设备正常运行需要能源的提供,当市电无法供电时,需要用油机发电,电源监控系统可以全面改善基站电源运行维护质量.在维护的过程中,要注意通信电源 ...查看


  • 基站电源维护知识点滴
  • 基站电源维护知识 移动通信近十多年来在我国的发展可以用超高速来描述也一点不为过,而作为通信的"心脏"电源的维护至关重要. 本文主要是探讨一下基站用直流供电系统的供电保证和维护问题. 一. 移动通信基站用直流供电系统 移动 ...查看


  • 格力空调各种型号的故障代码大全与故障维修资料
  • 格力空调各种型号的故障代码大全与故障维修资料 格力空调故障代码大全 (本信息由广州格力空调维修点提供发布,用户报修请拨打:020-82171053报修,更多格力空调维修技术文章请登录:net) 格力空调故障代码KF-60LWAK分体立柜式房 ...查看


  • 医院后勤细则
  • 医院后勤质量与安全管理细则 总则: 1.后勤要牢固树立为笫一线服务的思想,坚持下修.下送.下收.上门服务的态度,提高工作质量. 2.及时迅速.保质保量地组织好医院的财物管理.物质供应.设备维修.房屋修建,院容卫生等工作,保证医.教.研.防工 ...查看


  • 户外机柜安装规范
  • 一体化户外机柜 ----产品安装规范---- 目录 一. 新型室外一体化节能机柜产品简介 ........................................................................... ...查看


  • 基站故障处理流程
  • 基站故障处理流程图 一. 基站故障处理 ERROR LOG统计 在基站或者小区出现故障,但小区又没有退服的情况下,按照本手册进行处理.特别要求基站班故障处理派单人员在向县公司转派工单时,需要在工单中说明. (一) 对于影响网络运行指标或者用 ...查看


热门内容