ICS
点击此处添加中国标准文献分类号
DB
地
方
标
准
江西省
DB XX/ XXXXX—XXXX
公路隧道LED照明施工验收规范
Code for construction and acceptance of LED lighting in highway tunnel
(送审稿)
2013 - XX - XX发布 2013 - XX-XX实施
江西省质量技术监督局 发布
目 次
前言................................................................................II 引言...............................................................................III 1 范围..............................................................................1 2 规范性引用文件....................................................................1 3 术语和符号........................................................................1 4 一般规定..........................................................................1 5 基本要求项目验收..................................................................2 6 实测项目验收......................................................................4 7 验收合格评定......................................................................5 附录A(资料性附录) 验收评定用表....................................................1 条文说明.............................................................................1
前 言
本标准由江西省交通运输厅提出和归口。
本标准由江西赣粤高速公路股份有限公司、江西省交通运输厅南昌至铜鼓高速公路项目建设办公室、招商局重庆交通科研设计院有限公司负责起草。
本标准主要起草人:谭生光、王德山、杨全新、邹国平、吴志坚、涂久根、万阳、韩直、陈晓利、涂耘、周健、王小军、郭兴隆、谢耀华。
引 言
标准由江西赣粤高速公路股份有限公司负责解释。
各单位在使用过程中,若发现问题或有修改意见,请及时与主编单位江西赣粤高速公路股份有限公司联系(地址:江西省南昌市西湖区朝阳洲中路367号,邮编:330025,电话:0791-86507178,E-mail:[email protected]),以便修订时参考。
本标准为首次发布。
公路隧道LED照明施工验收规范
1 范围
本规范规定了公路隧道LED照明工程的验收原则、验收组织、验收程序、验收内容、验收方法。 本规范适用于江西省新建、改扩建高速公路隧道LED照明施工验收,其他等级公路隧道可参考执行。 2 规范性引用文件
下列文件对于本文件的应用是必不可少的。凡是注日期的引用文件,仅注日期的版本适用于本文件。凡是不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
JTG F80/2 公路工程质量检验评定标准 第二册 机电工程 JTJ 026.1 公路隧道通风照明设计规范 DBxx/xxxx 公路隧道LED照明设计规范 3 术语和符号
下列术语和定义适用于本文件。 3.1
路面平均亮度 average luminosity of road surface 规定测试区域内路面的平均亮度。 3.2
路面亮度总均匀度 overall uniformity of road surface luminance 规定测试区域最小照度(或亮度)与平均照度(或亮度)的比值。 3.3
路面亮度纵向均匀度 Longitudinal uniformity of road surface luminance 规定测试区域路面中线最小照度(或亮度)与最大照度(或亮度)的比值。 4 一般规定 4.1 验收条件
公路隧道LED照明工程施工验收应同时满足以下条件:
1) 施工方已完成公路隧道LED照明工程施工安装、软件编制、设备测试及系统调试工作; 2) 施工方和监理方完成对公路隧道LED照明工程的自检和抽检; 3) 自检、抽检中出现的问题已被解决;
4) 试运行期间,系统性能满足合同设计要求;
5) 施工方竣工资料齐备完整,满足合同规定的要求;
6) 符合政府或有关管理机构规定的其他任何竣工条件。
4.2 验收原则
4.2.1 公路隧道LED照明工程施工验收根据本规范的验收内容,参照国家、省部、行业、地方标准及合同双方约定的验收规程与指标,以竣工图为依据,以技术指标为功能评判的标准,开展验收工作。 4.2.2 公路隧道LED照明工程施工验收时间一般持续7个月。 4.3 验收组织
公路隧道LED照明工程施工验收由业主单位组织,应委托第三方具有隧道专项检验资格的单位进行施工验收,设计、监理、施工单位参与。 4.4 验收程序
公路隧道LED照明工程施工验收一般遵照图1所示程序:
图1 公路隧道LED照明工程施工验收程序
4.5 验收内容
公路隧道LED照明工程施工验收的内容包括基本要求验收和实测项目验收。 5 基本要求项目验收 5.1 资质文件验收
5.1.1 资质文件验收内容包括设计方、施工方、监理方、供应商、LED隧道照明灯具检验方(若应用的照明产品提供检测报告的,需查验LED隧道照明灯具检验方)的资质及质量管理体系文件。
5.1.2 资质文件验收主要查验相关单位是否具有承担相应业务的资质、是否建立完善的质量管理体系。 5.2 工程文件验收
5.2.1 工程文件主要内容包括设计文件、施工文件、监理文件、竣工文件。
表1 工程文件验收的主要内容
序号
1 2 3 4
验收项目 设计文件 施工文件 监理文件 竣工文件
具体内容
设计图、设计说明文件、设计审批文件、设计变更单等关键技
术、关键工艺的技术文件
施工图、施工说明文件、施工组织设计、施工规范、施工过程检验规范、采购规范、外购件质量检验和验收规范、工程测试大纲、
隐蔽工程验收记录等
监理规程和监理过程记录文件
系统使用说明书、培训资料、维护维修说明书、竣工图、竣工
决算等
技术要求 资料齐全 资料齐全 资料齐全 资料齐全
5.2.2 工程文件验收主要是查验相关技术文件和记录的完整性。 5.3 测试记录文件验收
5.3.1 测试记录文件包括灯具出厂合格证、LED灯具进场预检、自检、互检记录、电气照明器具及其配电箱(盘)安装分项工程质量检验评定记录、电气绝缘电阻测试记录。重点查验公路隧道LED灯技术条件中要求的指标项目测试文件。
5.3.2 测试记录文件验收主要是查验施工过程相关测试情况和记录的完整性。 5.4 系统完整性验收
5.4.1 系统完整性验收主要内容见表2。
表2 系统完整性验收内容
序号 1 2 3 4 5
验收项目 照明灯具 缆线 安装支架 亮度传感器 调光控制
验收要求
数量、型号规格、程式符合设计要求,部件及配件完整
结构尺寸、预埋件、安装方位、安装间距符合设计要求
类别、规格、使用场所、有效范围、数量、位置、安装间距、安装质量符合设计要
求
调光控制器控制范围、设置位置、通讯通路符合设计要求
5.4.2 系统完整性验收主要是查验公路隧道LED照明系统是否与设计图纸相符。 5.5 外观验收 5.5.1 外观验收的内容 外观验收内容见表3。
表3 外观验收内容
序号 1 2 3 4 5
验收项目 灯具安装 端头制作 线缆连接
楚;
设备表面 控制柜布线
预留长度适当;
设备表面光泽一致、无划伤、无刻痕、无剥落、无锈蚀
布线整齐、美观、绑扎牢固,接线端头焊(压)结牢固、平滑;编号标识清楚,
验收要求
灯具安装稳固、位置正确,灯具轮廓线形与隧道协调、美观
照明设备的电力线、信号线、接地线端头制作规范
按设计要求采取线缆保护措施、布线排列整齐美观、安装固定符合要求、标识清
6 7 8
控制柜柜门 控制柜箱内 灯具发光情况
开关灵活、出线孔密封措施得当 无积水、无霉变、无明显尘土、表面无锈蚀 照明灯具应发光均匀,无刺眼的眩光。
5.5.2 外观验收主要是通过目测方法检查公路隧道LED照明工程施工质量。 6 实测项目验收 6.1 测试项目
公路隧道LED照明工程验收实测项目见表4。
表4 照明工程实测项目
项次
检查项目
技术要求
符合设计要求。无要求时:纵向≤30mm,横向≤
1
灯具的安装偏差
20mm,高度≤10mm
尺测量
500V兆欧表测
2
△绝缘电阻
△控制柜安全保护接地电
3
阻
4 5 6
△防雷接地电阻 灯具启动时间的可调性 启动、停止方式
动、停止
△照度(人口段、过渡段、
7
中间段、出口段)
△照度总均匀度、纵向均匀
8
度
3000h
9
△光衰
6000h
≤8%
符合设计要求,若设计要求没有规定,直流驱动
10
△灯具效能
LED隧道灯灯具效能≥90lm/W,交流驱动LED隧道灯≥45lm/W。
双路供电照明系统,主供电路停电时,应自动切换
11
△紧急照明
到备用供电线路上
接收下端车辆检测器、亮度检测器传来的信息,做
12
调光控制计算机功能
出执行控制方案。其他设计规定的内容
实际操作 模拟操作 照度计
≤4%
照度计
符合设计要求
照度计
符合设计要求
照度计
≤10Ω
仪
照明回路组的启动时间间隔、可控
可自动、手动两种方式控制全部或部分照明器的启
实际操作 实际操作
≤4Ω
仪
接地电阻测量
强电端子对机壳≥50MΩ
量
接地电阻测量检查方法 用经伟仪或量
注:△表示关键项目
6.2 实测项目测试要求
6.2.1 公路隧道LED照明工程关键测试项目验收工作由业主委托的第三方具有隧道专项检测单位根据
验收大纲进行工程现场实测,测试原始数据作为验收报告的一部分。
6.2.2 对关键项目照度(表4第7项)、照度总均匀度、纵向均匀度(表4第8项)测试条件规定见表5:
表5 关键项目照度、照度总均匀度、纵向均匀度测试条件规定
序号 1 2 3
条件项 灯具运行时间 灯具测试时间 测试前准备工作
具体规定
灯具点亮1000小时后进行测试
夜间,开始测试时间以洞外自然光不直接照进隧道出入口为宜
测试前一周清洗隧道灯具,测试期间灯具处于洁净状态
7 验收合格评定 7.1 评分标准
公路隧道LED照明工程施工质量总分为100分。 基本要求项目验收总分为40分。
资质文件验收为5分,若有一项不符合要求则扣1分; 工程文件验收为4分,若有一项不符合要求则扣1分; 测试记录文件验收为9分,若有一项不符合要求扣3分; 系统完整性验收为6分,若有一项不符合要求则扣1分; 外观验收为16分,若有一项不符合要求则扣2分; 实测项目验收总分为60分,其中关键项目有一项不符合要求则扣12分,若其余项有一项不符合要求则扣4分。
7.2 验收合格判定
根据基本要求验收和关键检测项目验收的评分项进行累加,若累积分数≥90分,则工程合格,若累积分数≤90分,则工程需整改后再验收。对于不合格项,第三方检测单位应提出整改通知。 7.3 不合格项目处理
如出现某些功能或指标未达到要求,则由验收方开具整改通知,并在整改后再进行工程验收。 7.4 验收合格报告
验收合格的工程,由第三方具有检测资质的单位出具相关验收合格报告。
DBXX/ XXXXX—XXXX
附 录 A
(资料性附录) 验收评定用表 表A.1 基本要求验收评定表
项
验收项目
次
设计方 施工方
1
资质文件
监理方 供应商 LED照明检测方 设计文件
艺的技术文件
具有施工图、施工说明文件、施工组织设计、施工规范、施工过程检验规范、
2
工程文件
施工文件
采购规范、外购件质量检验和验收规范、工程测试大纲、隐蔽工程验收记录等
监理文件 竣工文件
3
文件
测试记录
进场检查 质量检测
具有监理规程和监理过程记录文件
具有系统使用说明书、培训资料、维护维修说明书、竣工图、竣工决算等
具有灯具出厂合格证、LED灯具进场预检、自检、互检记录 电气照明器具及其配电箱(盘)安装分项工程质量检验评定记录
资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整
共9分每项不合格扣3分
资料齐全、记录完整
共4分每项不合格扣1分
具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系
具有设计图、设计说明文件、设计审批文件、设计变更单等关键技术、关键工
资料齐全、记录完整
资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整
共5分每项不合格扣1分
具体内容
验收要求
准
评分标
评分
DBXX/ XXXXX—XXXX
安全检测
电气绝缘电阻测试记录
资料齐全、记录完整
共6分
照明灯具
数量、型号规格、程式符合设计要求,部件及配件完整
符合设计要求
不合格扣1分
线缆 安装支架
4
系统完整性
数量、型号规格、程式符合设计要求,部件及配件完整 结构尺寸、预埋件、安装方位、安装间距符合设计要求
类别、规格、使用场所、有效范围、数量、位置、安装间距、安装质量符合设
亮度检测器(可选)
计要求
类别、规格、使用场所、有效范围、数量、位置、安装间距、安装质量符合设
车辆检测器(可选)
计要求
调光控制器(可选)
调光控制器控制范围、设置位置、通讯通路符合设计要求
符合设计要求
共16分
灯具安装
灯具安装稳固、位置正确,灯具轮廓线形与隧道协调、美观
符合要求
不合格扣2分
端头制作
照明设备的电力线、信号线、接地线端头制作规范
按设计要求采取线缆保护措施、布线排列整齐美观、安装固定符合要求、标识
线缆连接
清楚
5
外观验收
设备表面
设备表面光泽一致、无划伤、无刻痕、无剥落、无锈蚀
布线整齐、美观、绑扎牢固,接线端头焊(压)结牢固、平滑;编号标识清楚,
控制柜布线
预留长度适当
控制柜柜门 控制柜箱内
灯具发光情况
开关灵活、出线孔密封措施得当 无积水、无霉变、无明显尘土、表面无锈蚀 照明灯具应发光均匀,无刺眼的眩光。
符合要求 符合要求 符合要求
符合要求
符合要求
符合要求
符合要求
符合设计要求
符合设计要求
符合设计要求 符合设计要求
DBXX/ XXXXX—XXXX
共40
合计
分
表A.2 实测项目验收评定表
项次 1 2 3 4 5 6 7 8
检查项目 灯具的安装偏差 △绝缘电阻 △控制柜安全保护接地
电阻
△防雷接地电阻 灯具启动时间的可调性
启动、停止方式 △照度(人口段、过渡段、中间段、出口段) △照度总均匀度、纵向均
匀度
3000h
9
△光衰
6000h
10 12 13
△灯具效能 △紧急照明 调光控制计算机功能
≤8%
照度计 模拟操作 实际操作
符合设计要求,若设计要求没有规定,直流驱动LED隧道灯灯具
效能≥90lm/W,交流驱动LED隧道灯≥45lm/W。 双路供电照明系统,主供电路停电时,应自动切换到备用供电线
路上 接收下端车辆检测器、亮度检测器传来的信息,做出执行控制方
案。其他设计规定的内容
合计
具体内容
符合设计要求。无要求时:纵向≤30mm,横向≤20mm,高度≤10mm
强电端子对机壳≥50MΩ
≤4Ω ≤10Ω
照明回路组的启动时间间隔、可控
可自动、手动两种方式控制全部或部分照明器的启动、停止
满足设计要求 符合设计要求
≤4%
照度计 检查方法 用经伟仪或
量尺测量 500V兆欧表测量 接地电阻测量仪 接地电阻测量仪 实际操作 实际操作 照度计 照度计
采用扣分制,原始总分60,关键项目有一项不符合要求则扣12分,其余项有一项不符合要求则扣4分
评分标准
评分
DBXX/ XXXXX—XXXX
附件:
条文说明
1 范围
本条规定了标准的使用范围。本标准只用于江西省新建、改扩建高速隧道LED照明的施工和验收,其他隧道LED照明施工验收也可参考本标准。
3 术语和定义
3.1 路面平均亮度
隧道照明的路面平均亮度是在规定测试区域内的路面平均亮度,往往取同侧相邻的两个灯具构成的一个灯具周期内的路面照明区域作为测试区域。在该区域内选择一系列的网格点,通过测试每个网格点的亮度,对所有网格点的亮度取平均从而得到该区域的路面平均亮度。
3.2 路面亮度总均匀度
路面亮度总均匀度是规定测试区域内最小亮度与最大亮度的比值。在验收测试时,通常取测试区域内一系列网格点中最小亮度与最大亮度之比。该值体现了路面亮度的总体舒适度水平。
3.3 路面亮度纵向匀度
路面亮度纵向均匀度是规定测试区域内每一车道路面中线的最小亮度与最大亮度的比值。该值用于体现在行驶过程中的路面照明舒适度,可避免“斑马效应”的出现。在施工验收测试就对不同车道位置的路面亮度纵向均匀度进行测试。
4 一般规定
4.1 验收条件
验收条件是对隧道LED照明施工能否进行验收的最基本的参考依据,只有符合这系列条件,才能开展相应的验收工作。在开始验收工作之前,应对这些条件进行考察,保证验收工作的顺利开展。
4.2 验收原则
验收原则是验收结果评定的依据,包括各种资质文件及系列测试的技术指标。验收过程要体现“公开、公正、公平”的原则。
5 基本要求项目验收
5.3 测试记录文件验收
测试记录文件验收是对施工前期工作的考核,评定施工工程在灯具选用的合理性、灯具安装的规范性和安全性及技术操作上的规范完整性。测试记录文件的完整性与否直接会影响到后期照明施工的质量。
5.4 系统完整性验收
测试记录文件验收是对施工前期工作的考核,评定施工工程在灯具选用的合理性、灯具安装的规范
DBXX/ XXXXX—XXXX
性和安全性及技术操作上的规范完整性。测试记录文件的完整性与否直接会影响到后期照明施工的质量。
5.5 外观验收
外观验收主要用于检查灯具在安装过程中是否符合工程施工的质量要求,是否满足安全性及规范性要求。外观验收由验收人员根据实作经验通过目测及手动操作来判断设备安装是否达到标准。
6 实测项目验收
6.1 测试项目
实测项目中的光学参数应是标准中所规定的参数,其中部分参数是在测量后通过计算取得的。测试所用的仪器设备必须送法定检测机构依据相关检定规程进行送检,以保证检测数据的有效性。其中照明测量的测点,须根据一个布灯周期的网格划分法进行网格划分取测点。
6.2 实测项目测试要求
6.2.2中对于照度指标的测量需使灯具达到稳定状态之后开始测量,从而消除由于LED灯具在开始点亮的较短时间内存在的不稳定因素,通常当LED点亮1000小时后,其光效基本达到稳定。并且要消除自然光对灯具照明效果的影响。为了达到准确的测试结果,在测试前一周内须清洁灯具,从而消除由于灯具表面的附着物对灯具出射光分布的影响。
ICS
点击此处添加中国标准文献分类号
DB
地
方
标
准
江西省
DB XX/ XXXXX—XXXX
公路隧道LED照明施工验收规范
Code for construction and acceptance of LED lighting in highway tunnel
(送审稿)
2013 - XX - XX发布 2013 - XX-XX实施
江西省质量技术监督局 发布
目 次
前言................................................................................II 引言...............................................................................III 1 范围..............................................................................1 2 规范性引用文件....................................................................1 3 术语和符号........................................................................1 4 一般规定..........................................................................1 5 基本要求项目验收..................................................................2 6 实测项目验收......................................................................4 7 验收合格评定......................................................................5 附录A(资料性附录) 验收评定用表....................................................1 条文说明.............................................................................1
前 言
本标准由江西省交通运输厅提出和归口。
本标准由江西赣粤高速公路股份有限公司、江西省交通运输厅南昌至铜鼓高速公路项目建设办公室、招商局重庆交通科研设计院有限公司负责起草。
本标准主要起草人:谭生光、王德山、杨全新、邹国平、吴志坚、涂久根、万阳、韩直、陈晓利、涂耘、周健、王小军、郭兴隆、谢耀华。
引 言
标准由江西赣粤高速公路股份有限公司负责解释。
各单位在使用过程中,若发现问题或有修改意见,请及时与主编单位江西赣粤高速公路股份有限公司联系(地址:江西省南昌市西湖区朝阳洲中路367号,邮编:330025,电话:0791-86507178,E-mail:[email protected]),以便修订时参考。
本标准为首次发布。
公路隧道LED照明施工验收规范
1 范围
本规范规定了公路隧道LED照明工程的验收原则、验收组织、验收程序、验收内容、验收方法。 本规范适用于江西省新建、改扩建高速公路隧道LED照明施工验收,其他等级公路隧道可参考执行。 2 规范性引用文件
下列文件对于本文件的应用是必不可少的。凡是注日期的引用文件,仅注日期的版本适用于本文件。凡是不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
JTG F80/2 公路工程质量检验评定标准 第二册 机电工程 JTJ 026.1 公路隧道通风照明设计规范 DBxx/xxxx 公路隧道LED照明设计规范 3 术语和符号
下列术语和定义适用于本文件。 3.1
路面平均亮度 average luminosity of road surface 规定测试区域内路面的平均亮度。 3.2
路面亮度总均匀度 overall uniformity of road surface luminance 规定测试区域最小照度(或亮度)与平均照度(或亮度)的比值。 3.3
路面亮度纵向均匀度 Longitudinal uniformity of road surface luminance 规定测试区域路面中线最小照度(或亮度)与最大照度(或亮度)的比值。 4 一般规定 4.1 验收条件
公路隧道LED照明工程施工验收应同时满足以下条件:
1) 施工方已完成公路隧道LED照明工程施工安装、软件编制、设备测试及系统调试工作; 2) 施工方和监理方完成对公路隧道LED照明工程的自检和抽检; 3) 自检、抽检中出现的问题已被解决;
4) 试运行期间,系统性能满足合同设计要求;
5) 施工方竣工资料齐备完整,满足合同规定的要求;
6) 符合政府或有关管理机构规定的其他任何竣工条件。
4.2 验收原则
4.2.1 公路隧道LED照明工程施工验收根据本规范的验收内容,参照国家、省部、行业、地方标准及合同双方约定的验收规程与指标,以竣工图为依据,以技术指标为功能评判的标准,开展验收工作。 4.2.2 公路隧道LED照明工程施工验收时间一般持续7个月。 4.3 验收组织
公路隧道LED照明工程施工验收由业主单位组织,应委托第三方具有隧道专项检验资格的单位进行施工验收,设计、监理、施工单位参与。 4.4 验收程序
公路隧道LED照明工程施工验收一般遵照图1所示程序:
图1 公路隧道LED照明工程施工验收程序
4.5 验收内容
公路隧道LED照明工程施工验收的内容包括基本要求验收和实测项目验收。 5 基本要求项目验收 5.1 资质文件验收
5.1.1 资质文件验收内容包括设计方、施工方、监理方、供应商、LED隧道照明灯具检验方(若应用的照明产品提供检测报告的,需查验LED隧道照明灯具检验方)的资质及质量管理体系文件。
5.1.2 资质文件验收主要查验相关单位是否具有承担相应业务的资质、是否建立完善的质量管理体系。 5.2 工程文件验收
5.2.1 工程文件主要内容包括设计文件、施工文件、监理文件、竣工文件。
表1 工程文件验收的主要内容
序号
1 2 3 4
验收项目 设计文件 施工文件 监理文件 竣工文件
具体内容
设计图、设计说明文件、设计审批文件、设计变更单等关键技
术、关键工艺的技术文件
施工图、施工说明文件、施工组织设计、施工规范、施工过程检验规范、采购规范、外购件质量检验和验收规范、工程测试大纲、
隐蔽工程验收记录等
监理规程和监理过程记录文件
系统使用说明书、培训资料、维护维修说明书、竣工图、竣工
决算等
技术要求 资料齐全 资料齐全 资料齐全 资料齐全
5.2.2 工程文件验收主要是查验相关技术文件和记录的完整性。 5.3 测试记录文件验收
5.3.1 测试记录文件包括灯具出厂合格证、LED灯具进场预检、自检、互检记录、电气照明器具及其配电箱(盘)安装分项工程质量检验评定记录、电气绝缘电阻测试记录。重点查验公路隧道LED灯技术条件中要求的指标项目测试文件。
5.3.2 测试记录文件验收主要是查验施工过程相关测试情况和记录的完整性。 5.4 系统完整性验收
5.4.1 系统完整性验收主要内容见表2。
表2 系统完整性验收内容
序号 1 2 3 4 5
验收项目 照明灯具 缆线 安装支架 亮度传感器 调光控制
验收要求
数量、型号规格、程式符合设计要求,部件及配件完整
结构尺寸、预埋件、安装方位、安装间距符合设计要求
类别、规格、使用场所、有效范围、数量、位置、安装间距、安装质量符合设计要
求
调光控制器控制范围、设置位置、通讯通路符合设计要求
5.4.2 系统完整性验收主要是查验公路隧道LED照明系统是否与设计图纸相符。 5.5 外观验收 5.5.1 外观验收的内容 外观验收内容见表3。
表3 外观验收内容
序号 1 2 3 4 5
验收项目 灯具安装 端头制作 线缆连接
楚;
设备表面 控制柜布线
预留长度适当;
设备表面光泽一致、无划伤、无刻痕、无剥落、无锈蚀
布线整齐、美观、绑扎牢固,接线端头焊(压)结牢固、平滑;编号标识清楚,
验收要求
灯具安装稳固、位置正确,灯具轮廓线形与隧道协调、美观
照明设备的电力线、信号线、接地线端头制作规范
按设计要求采取线缆保护措施、布线排列整齐美观、安装固定符合要求、标识清
6 7 8
控制柜柜门 控制柜箱内 灯具发光情况
开关灵活、出线孔密封措施得当 无积水、无霉变、无明显尘土、表面无锈蚀 照明灯具应发光均匀,无刺眼的眩光。
5.5.2 外观验收主要是通过目测方法检查公路隧道LED照明工程施工质量。 6 实测项目验收 6.1 测试项目
公路隧道LED照明工程验收实测项目见表4。
表4 照明工程实测项目
项次
检查项目
技术要求
符合设计要求。无要求时:纵向≤30mm,横向≤
1
灯具的安装偏差
20mm,高度≤10mm
尺测量
500V兆欧表测
2
△绝缘电阻
△控制柜安全保护接地电
3
阻
4 5 6
△防雷接地电阻 灯具启动时间的可调性 启动、停止方式
动、停止
△照度(人口段、过渡段、
7
中间段、出口段)
△照度总均匀度、纵向均匀
8
度
3000h
9
△光衰
6000h
≤8%
符合设计要求,若设计要求没有规定,直流驱动
10
△灯具效能
LED隧道灯灯具效能≥90lm/W,交流驱动LED隧道灯≥45lm/W。
双路供电照明系统,主供电路停电时,应自动切换
11
△紧急照明
到备用供电线路上
接收下端车辆检测器、亮度检测器传来的信息,做
12
调光控制计算机功能
出执行控制方案。其他设计规定的内容
实际操作 模拟操作 照度计
≤4%
照度计
符合设计要求
照度计
符合设计要求
照度计
≤10Ω
仪
照明回路组的启动时间间隔、可控
可自动、手动两种方式控制全部或部分照明器的启
实际操作 实际操作
≤4Ω
仪
接地电阻测量
强电端子对机壳≥50MΩ
量
接地电阻测量检查方法 用经伟仪或量
注:△表示关键项目
6.2 实测项目测试要求
6.2.1 公路隧道LED照明工程关键测试项目验收工作由业主委托的第三方具有隧道专项检测单位根据
验收大纲进行工程现场实测,测试原始数据作为验收报告的一部分。
6.2.2 对关键项目照度(表4第7项)、照度总均匀度、纵向均匀度(表4第8项)测试条件规定见表5:
表5 关键项目照度、照度总均匀度、纵向均匀度测试条件规定
序号 1 2 3
条件项 灯具运行时间 灯具测试时间 测试前准备工作
具体规定
灯具点亮1000小时后进行测试
夜间,开始测试时间以洞外自然光不直接照进隧道出入口为宜
测试前一周清洗隧道灯具,测试期间灯具处于洁净状态
7 验收合格评定 7.1 评分标准
公路隧道LED照明工程施工质量总分为100分。 基本要求项目验收总分为40分。
资质文件验收为5分,若有一项不符合要求则扣1分; 工程文件验收为4分,若有一项不符合要求则扣1分; 测试记录文件验收为9分,若有一项不符合要求扣3分; 系统完整性验收为6分,若有一项不符合要求则扣1分; 外观验收为16分,若有一项不符合要求则扣2分; 实测项目验收总分为60分,其中关键项目有一项不符合要求则扣12分,若其余项有一项不符合要求则扣4分。
7.2 验收合格判定
根据基本要求验收和关键检测项目验收的评分项进行累加,若累积分数≥90分,则工程合格,若累积分数≤90分,则工程需整改后再验收。对于不合格项,第三方检测单位应提出整改通知。 7.3 不合格项目处理
如出现某些功能或指标未达到要求,则由验收方开具整改通知,并在整改后再进行工程验收。 7.4 验收合格报告
验收合格的工程,由第三方具有检测资质的单位出具相关验收合格报告。
DBXX/ XXXXX—XXXX
附 录 A
(资料性附录) 验收评定用表 表A.1 基本要求验收评定表
项
验收项目
次
设计方 施工方
1
资质文件
监理方 供应商 LED照明检测方 设计文件
艺的技术文件
具有施工图、施工说明文件、施工组织设计、施工规范、施工过程检验规范、
2
工程文件
施工文件
采购规范、外购件质量检验和验收规范、工程测试大纲、隐蔽工程验收记录等
监理文件 竣工文件
3
文件
测试记录
进场检查 质量检测
具有监理规程和监理过程记录文件
具有系统使用说明书、培训资料、维护维修说明书、竣工图、竣工决算等
具有灯具出厂合格证、LED灯具进场预检、自检、互检记录 电气照明器具及其配电箱(盘)安装分项工程质量检验评定记录
资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整
共9分每项不合格扣3分
资料齐全、记录完整
共4分每项不合格扣1分
具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系 具有承担相应业务的资质,建立了完善的质量管理体系
具有设计图、设计说明文件、设计审批文件、设计变更单等关键技术、关键工
资料齐全、记录完整
资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整 资料齐全、记录完整
共5分每项不合格扣1分
具体内容
验收要求
准
评分标
评分
DBXX/ XXXXX—XXXX
安全检测
电气绝缘电阻测试记录
资料齐全、记录完整
共6分
照明灯具
数量、型号规格、程式符合设计要求,部件及配件完整
符合设计要求
不合格扣1分
线缆 安装支架
4
系统完整性
数量、型号规格、程式符合设计要求,部件及配件完整 结构尺寸、预埋件、安装方位、安装间距符合设计要求
类别、规格、使用场所、有效范围、数量、位置、安装间距、安装质量符合设
亮度检测器(可选)
计要求
类别、规格、使用场所、有效范围、数量、位置、安装间距、安装质量符合设
车辆检测器(可选)
计要求
调光控制器(可选)
调光控制器控制范围、设置位置、通讯通路符合设计要求
符合设计要求
共16分
灯具安装
灯具安装稳固、位置正确,灯具轮廓线形与隧道协调、美观
符合要求
不合格扣2分
端头制作
照明设备的电力线、信号线、接地线端头制作规范
按设计要求采取线缆保护措施、布线排列整齐美观、安装固定符合要求、标识
线缆连接
清楚
5
外观验收
设备表面
设备表面光泽一致、无划伤、无刻痕、无剥落、无锈蚀
布线整齐、美观、绑扎牢固,接线端头焊(压)结牢固、平滑;编号标识清楚,
控制柜布线
预留长度适当
控制柜柜门 控制柜箱内
灯具发光情况
开关灵活、出线孔密封措施得当 无积水、无霉变、无明显尘土、表面无锈蚀 照明灯具应发光均匀,无刺眼的眩光。
符合要求 符合要求 符合要求
符合要求
符合要求
符合要求
符合要求
符合设计要求
符合设计要求
符合设计要求 符合设计要求
DBXX/ XXXXX—XXXX
共40
合计
分
表A.2 实测项目验收评定表
项次 1 2 3 4 5 6 7 8
检查项目 灯具的安装偏差 △绝缘电阻 △控制柜安全保护接地
电阻
△防雷接地电阻 灯具启动时间的可调性
启动、停止方式 △照度(人口段、过渡段、中间段、出口段) △照度总均匀度、纵向均
匀度
3000h
9
△光衰
6000h
10 12 13
△灯具效能 △紧急照明 调光控制计算机功能
≤8%
照度计 模拟操作 实际操作
符合设计要求,若设计要求没有规定,直流驱动LED隧道灯灯具
效能≥90lm/W,交流驱动LED隧道灯≥45lm/W。 双路供电照明系统,主供电路停电时,应自动切换到备用供电线
路上 接收下端车辆检测器、亮度检测器传来的信息,做出执行控制方
案。其他设计规定的内容
合计
具体内容
符合设计要求。无要求时:纵向≤30mm,横向≤20mm,高度≤10mm
强电端子对机壳≥50MΩ
≤4Ω ≤10Ω
照明回路组的启动时间间隔、可控
可自动、手动两种方式控制全部或部分照明器的启动、停止
满足设计要求 符合设计要求
≤4%
照度计 检查方法 用经伟仪或
量尺测量 500V兆欧表测量 接地电阻测量仪 接地电阻测量仪 实际操作 实际操作 照度计 照度计
采用扣分制,原始总分60,关键项目有一项不符合要求则扣12分,其余项有一项不符合要求则扣4分
评分标准
评分
DBXX/ XXXXX—XXXX
附件:
条文说明
1 范围
本条规定了标准的使用范围。本标准只用于江西省新建、改扩建高速隧道LED照明的施工和验收,其他隧道LED照明施工验收也可参考本标准。
3 术语和定义
3.1 路面平均亮度
隧道照明的路面平均亮度是在规定测试区域内的路面平均亮度,往往取同侧相邻的两个灯具构成的一个灯具周期内的路面照明区域作为测试区域。在该区域内选择一系列的网格点,通过测试每个网格点的亮度,对所有网格点的亮度取平均从而得到该区域的路面平均亮度。
3.2 路面亮度总均匀度
路面亮度总均匀度是规定测试区域内最小亮度与最大亮度的比值。在验收测试时,通常取测试区域内一系列网格点中最小亮度与最大亮度之比。该值体现了路面亮度的总体舒适度水平。
3.3 路面亮度纵向匀度
路面亮度纵向均匀度是规定测试区域内每一车道路面中线的最小亮度与最大亮度的比值。该值用于体现在行驶过程中的路面照明舒适度,可避免“斑马效应”的出现。在施工验收测试就对不同车道位置的路面亮度纵向均匀度进行测试。
4 一般规定
4.1 验收条件
验收条件是对隧道LED照明施工能否进行验收的最基本的参考依据,只有符合这系列条件,才能开展相应的验收工作。在开始验收工作之前,应对这些条件进行考察,保证验收工作的顺利开展。
4.2 验收原则
验收原则是验收结果评定的依据,包括各种资质文件及系列测试的技术指标。验收过程要体现“公开、公正、公平”的原则。
5 基本要求项目验收
5.3 测试记录文件验收
测试记录文件验收是对施工前期工作的考核,评定施工工程在灯具选用的合理性、灯具安装的规范性和安全性及技术操作上的规范完整性。测试记录文件的完整性与否直接会影响到后期照明施工的质量。
5.4 系统完整性验收
测试记录文件验收是对施工前期工作的考核,评定施工工程在灯具选用的合理性、灯具安装的规范
DBXX/ XXXXX—XXXX
性和安全性及技术操作上的规范完整性。测试记录文件的完整性与否直接会影响到后期照明施工的质量。
5.5 外观验收
外观验收主要用于检查灯具在安装过程中是否符合工程施工的质量要求,是否满足安全性及规范性要求。外观验收由验收人员根据实作经验通过目测及手动操作来判断设备安装是否达到标准。
6 实测项目验收
6.1 测试项目
实测项目中的光学参数应是标准中所规定的参数,其中部分参数是在测量后通过计算取得的。测试所用的仪器设备必须送法定检测机构依据相关检定规程进行送检,以保证检测数据的有效性。其中照明测量的测点,须根据一个布灯周期的网格划分法进行网格划分取测点。
6.2 实测项目测试要求
6.2.2中对于照度指标的测量需使灯具达到稳定状态之后开始测量,从而消除由于LED灯具在开始点亮的较短时间内存在的不稳定因素,通常当LED点亮1000小时后,其光效基本达到稳定。并且要消除自然光对灯具照明效果的影响。为了达到准确的测试结果,在测试前一周内须清洁灯具,从而消除由于灯具表面的附着物对灯具出射光分布的影响。